Instruction Book
120
9828 0934 73
*)
Cooling water flow at
25 ˚C (77 ˚F) water inlet (approx.) and a temperature difference of 10 ˚C (18 ˚F).
Performance data with cooling water inlet of 40 °C (104 °F)
Unit
At ambient temperature
of:
°C
25
30
35
40
At ambient temperature
of:
°F
77
86
95
104
Volume flow at dryer
inlet under nominal
conditions
l/s
510
510
510
510
Volume flow at dryer
inlet under nominal
conditions
cfm
1080.63
1080.63
1080.63
1080.63
Pressure dew-point
˚C
3
4
10
17
Pressure dew-point
˚F
37.4
39.2
50
62.6
Total power
consumption
kW
4.2
4.3
4.3
4.4
Total power
consumption
hp
5.63
5.77
5.77
5.9
Cooling water flow
(approx.) *)
l/s
1.2
1.3
1.4
1.5
Cooling water flow
(approx.) *)
cfm
2.54
2.75
2.97
3.18
Heat dissipated by
cooling water flow
(approx.)
kW
13
16
17
19
Heat dissipated by
cooling water flow
Btu/hr
44369
54608
58021
64847
Cooling water flow at
40 ˚C (104 ˚F) water inlet (approx.) and a temperature difference of 3 ˚C (5.4 ˚F).
QED-1050 (E
S 510
)
water-cooled, 60 Hz, version
Performance data with cooling water inlet of 25 °C (77 °F)
Unit
At ambient temperature
of:
°C
25
30
35
40
At ambient temperature
of:
°F
77
86
95
104
Volume flow at dryer inlet
under nominal conditions
l/s
510
510
510
510
Volume flow at dryer inlet
under nominal conditions
cfm
1080.63
1080.63
1080.63
1080.63
Pressure dew-point
˚C
2
3
6
12
Pressure dew-point
˚F
35.6
37.4
42.8
53.6
Total power
consumption
kW
4
4
4
4
Total power
consumption
hp
5.36
5.36
5.36
5.36