background image

Instruction Book 

52 

9828 0934 73 

Move the cursor to the action button Menu and press the Enter key. Following screen appears:

Using the Scroll keys, move the cursor to the Event History icon (see above, section Menu icon).

The list of last shut-down and emergency stop cases is shown.

Scroll through the items to select the desired shut-down or emergency stop event.

Press the Enter key to find the date, time and other data reflecting the status of the dryer when
that shut- down or emergency stop occurred.

3.10  Modifying settings 

Control panel 

(1)

 

Enter key

 

(2)

 

Escape key

 

(3)

 

Scroll keys

 

Menu icon, Settings

 

Function

 

To display and modify a number of settings (e.g. Time, Date, Date format, Language, units ...). 

Procedure 

Starting from the Main screen (see 

Main screen

), 

Move the cursor to the action button Menu and press the Enter key. Following screen appears:

Summary of Contents for QED 1050

Page 1: ...Quincy Refrigerant compressed air dryers QED 650 QED 850 QED 1050 QPVS 650 QPVS 850 QPVS 1050 Air Cooled and Water Cooled Instruction book...

Page 2: ......

Page 3: ...Belgium Any unauthorized use or copying of the contents or any part thereof is prohibited This applies in particular to trademarks model denominations part numbers and drawings Use only authorized pa...

Page 4: ...Instruction Book 4 9828 0934 73...

Page 5: ...uit 21 2 3 Refrigeration system 26 2 4 Automatic regulation system 31 2 5 Condensate drain system 35 2 6 Electrical system 37 3 Controller 38 3 1 General 38 3 2 Control panel 39 3 3 Icon used 40 3 4 M...

Page 6: ...Initial start up 101 5 3 Starting 102 5 4 During operation 102 5 5 Stopping 103 6 Maintenance 104 6 1 Preventive maintenance schedule 104 7 Problem solving 106 7 1 Problem solving 106 7 1 1 Faults and...

Page 7: ...t be adequately purified according to the applicable legislation and standards 5 Before any maintenance repair work adjustment or any other non routine checks Stop the compressor Press the emergency s...

Page 8: ...explosion 7 Arrange the air intake so that loose clothing worn by people cannot be sucked in 8 Ensure that the discharge pipe from the dryer to the air net is free to expand under heat and that it is...

Page 9: ...hen blowing through a hose or air line ensure that the open end is held securely A free end will whip and may cause injury Make sure that a hose is fully depressurized before disconnecting it 3 Person...

Page 10: ...ce work shall only be undertaken when the machine has cooled down 5 A warning sign bearing a legend such as Work in progress do not start shall be attached to the starting equipment 6 Persons switchin...

Page 11: ...the skin rinse the skin with water If liquid refrigerant contacts the skin through clothing never tear off or remove the latter flush abundantly with fresh water over the clothing until all refrigera...

Page 12: ...ive 2012 19 EU with the crossed out wheelie bin symbol At the end of life time of the electric and electronic equipment EEE it must be taken to separate collection For more information check with your...

Page 13: ...gulator 1 keeps the pressure dew point stable at no load by opening or closing the solenoid valve of the hot gas by pass On air cooled dryers the condenser has a cooling fan controlled by a pressure s...

Page 14: ...Instruction Book 14 9828 0934 73 General view of water cooled QED QPVS dryer Reference Description 1 Electronic regulator 2 Grating Position of components Inside view of air cooled QED 650 ES 310...

Page 15: ...Instruction Book 9828 0934 73 15 Inside view of air cooled QED 850 ES 410 Inside view of air cooled QPVS 650 ES 310 VSD and QPVS 850 410 VSD...

Page 16: ...Instruction Book 16 9828 0934 73 Inside view air cooled QED 1050 ES 510 Inside view air cooled QPVS 1050 ES 510 VSD...

Page 17: ...Instruction Book 9828 0934 73 17 Inside view of water cooled QED 650 ES 310 Inside view of water cooled QPVS 650 ES 310 VSD and QPVS 850 ES 410 VSD...

Page 18: ...Instruction Book 18 9828 0934 73 Inside view of water cooled QED 850 ES 410 and QED 1050 ES 510 Inside view of water cooled QPVS 1050 ES 510 VSD...

Page 19: ...ryers air cooled condenser On water cooled dryers water cooled condenser 4 Solenoid valve 5 Cubicle 6 Hot gas by pass valve 7 Refrigerant compressor 8 Liquid separator 9 Electronic water drain 10 Sigh...

Page 20: ...of water cooled dryer Reference Name 1 Compressed air outlet 2 Compressed air inlet 3 Cable gland electrical connection 4 Automatic drain hose 5 Cooling water outlet Only on water cooled dryers 6 Cool...

Page 21: ...Instruction Book 9828 0934 73 21 2 2 Air circuit Air Flow diagram Air and refrigerant flow diagram for air cooled QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 22: ...Instruction Book 22 9828 0934 73 Air and refrigerant flow diagram for air cooled QPVS 650 ES 310 VSD QPVS 850 ES 410 VSD and QPVS 1050 ES 510 VSD...

Page 23: ...Instruction Book 9828 0934 73 23 Air and refrigerant flow diagram for water cooled QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 24: ...Instruction Book 24 9828 0934 73 Air and refrigerant flow diagram for water cooled QPVS 650 ES 310 VSD QPVS 850 ES 410 VSD and QPVS 1050 ES 510 VSD...

Page 25: ...Enclosure for several components assembled in one unit Second fan blower is installed on QED 1050 ES 510 46 C 115 F Description Compressed air enters heat exchanger 101a and is cooled by the outgoing...

Page 26: ...Instruction Book 26 9828 0934 73 2 3 Refrigeration system Refrigerant flow diagram Air and refrigerant flow diagram for QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 27: ...Instruction Book 9828 0934 73 27 Air and refrigerant flow diagram for air cooled QPVS 650 ES 310 VSD QPVS 850 ES 410 VSD and QPVS 1050 ES 510 VSD...

Page 28: ...Instruction Book 28 9828 0934 73 Air and refrigerant flow diagram for water cooled QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 29: ...Instruction Book 9828 0934 73 29 Air and refrigerant flow diagram for water cooled QPVS 650 ES 310 VSD QPVS 850 ES 410 VSD and QPVS 1050 ES 510 VSD...

Page 30: ...pressure The heated refrigerant leaves the evaporator and is sucked in by refrigerant compressor 209 via liquid separator 207 The dryers are provided with a sight glass 211 The sight glass allows the...

Page 31: ...Instruction Book 9828 0934 73 31 2 4 Automatic regulation system Air and refrigerant flow diagram Air and refrigerant flow diagram for air cooled QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 32: ...Instruction Book 32 9828 0934 73 Air and refrigerant flow diagram for air cooled QPVS 650 ES 310 VSD QPVS 850 ES 410 VSD and QPVS 1050 ES 510 VSD...

Page 33: ...Instruction Book 9828 0934 73 33 Air and refrigerant flow diagram for water cooled QED 650 ES 310 QED 850 ES 410 and QED 1050 ES 510...

Page 34: ...versions the regulator stops and starts the cooling fans For water cooled versions the water regulating valve in the water outlet regulates the cooling water flow When at partial or no load the dew p...

Page 35: ...934 73 35 2 5 Condensate drain system Description Electronic water drain location Electronic water drain functioning Reference Name 1 Inlet 2 Supply line 3 Pilot valve 4 Diaphragm 5 Sensor 6 Collector...

Page 36: ...water drain starts flashing a warning appears on the display of the regulator and the electronic drain valve will automatically change to the alarm mode opening and closing the valve according to a se...

Page 37: ...e compressor motor when the pressure in the refrigerant circuit reaches the upper set point of the switch After tripping The switch must be reset manually by pressing its reset knob and by accessing t...

Page 38: ...general the regulator has following functions controlling the dryer protecting the dryer automatic restart after voltage failure made inactive Controlling the dryer The regulator keeps the pressure d...

Page 39: ...oltage A restart delay can also be programmed allowing for example the dryer and the compressors to be restarted one after the other 3 2 Control panel Parts and functions Reference Designation Functio...

Page 40: ...nds still When the dryer is running the icon is rotating Machine control mode Local start stop Remote start stop Network control Automatic restart after voltage failure Automatic restart after voltage...

Page 41: ...4 73 41 Inputs Icons Icon Description Pressure Temperature Digital input Special protection System Icons Icon Description Dryer Fan Frequency converter Drain Filter Motor Failure expansion module Netw...

Page 42: ...Menu icons Icon Description Inputs Outputs Alarms Warnings shutdowns Counters Test Settings Service Event history saved data Access key User password Network Set point Info General settings Navigation...

Page 43: ...Main screen is shown automatically when the voltage is switched on and one of the keys is pushed It is switched off automatically after a few minutes when no keys are pushed Five different main screen...

Page 44: ...rresponds to the selected icon When the menu button is selected this text shows the operational state of the dryer Section D shows the Action buttons These buttons are used to call up or program setti...

Page 45: ...or selecting other screens is changed into a small Chart and is highlighted active When the Chart Low Resolution is selected a chart showing the parameter per day is shown on the main screen Each poin...

Page 46: ...the Scroll keys Press the Enter key to select the menu Following screen appears The screen shows a number of icons Each icon indicates a menu item By default the Inputs icon is selected The status bar...

Page 47: ...To call up information regarding the actually measured data and the status of some inputs such as the Vessel Pressure Procedure Starting from the main screen see Main screen Move the cursor to the ac...

Page 48: ...he first items of a list of all inputs with their corresponding icons and readings Use the scroll button to see the other items in the list If an input is in warning or shutdown the original icon is r...

Page 49: ...appears Move the cursor to the Outputs icon using the Scroll keys Press the Enter key A screen similar to the one below appears 1 Outputs 2 Solenoid Valve 1 HGBP1 3 Run Enable Dryer Motor 4 Dryer Fan...

Page 50: ...number of dryer starts The number of hours that the regulator has been powered Procedure Starting from the Main screen see Main screen Move the cursor to the action button Menu and press the Enter ke...

Page 51: ...ule hours The screen shows a list of all counters with their actual readings 3 9 Event history menu Control panel 1 Scroll keys 2 Enter key 3 Escape key Menu icon Event History Function To call up the...

Page 52: ...desired shut down or emergency stop event Press the Enter key to find the date time and other data reflecting the status of the dryer when that shut down or emergency stop occurred 3 10 Modifying sett...

Page 53: ...nu icon Press the Enter key Following screen appears The screen shows a number of icons Icon Function Network settings General settings Regulation settings Automatic restart after voltage failure sett...

Page 54: ...ollowing screen appears Text on figure 1 Network 2 Ethernet 3 CAN A red selection bar is covering the first item Ethernet Use the key of the Scroll keys to select the setting to be modified and press...

Page 55: ...ng the Scroll keys move the cursor to the setting to be modified e g Ethernet and press the Enter button 2 A pop up screen appears Use the or key to select the required parameter and press the Enter k...

Page 56: ...of a list of all settings Use the scroll button to see the other items in the list Press the Enter button 2 a selection bar is covering the first item Dryer operation mode Use the key of the Scroll k...

Page 57: ...using the scroll key Press the enter button Press the enter button again to modify the security level Press the enter button again a pop up menu appears Use the scroll keys to enter the password of th...

Page 58: ...difying the chart range Select the chart range as described above and proceed as follows Press the enter key the minimum setting becomes highlighted Press the enter key to modify the minimum setting o...

Page 59: ...n To show the internet address Procedure Starting from the Main screen see Main screen Move the cursor to the action button Menu and press the Enter key Following screen appears Using the Scroll keys...

Page 60: ...k schemes can be programmed A week cycle can be programmed a week cycle is a sequence of 10 weeks For each week in the cycle one of the four programmed week schemes can be chosen Procedure Starting fr...

Page 61: ...Programming week schemes Select Week action schemes and press Enter A new window opens The first item in the list is highlighted in red Press the Enter key on the controller to modify Week Action Sche...

Page 62: ...the controller to create an action Text on figure 1 Monday 2 Modify A new pop up window opens Select an action from this list by using the Scroll keys on the controller When ready press the Enter key...

Page 63: ...window opens Use the or key of Scroll keys to modify the values of the hours Use the or Scroll keys to modify the minutes Text on figure 1 Monday 2 Time 3 Save 4 Modify Press the Escape key on the con...

Page 64: ...ns Press the Enter key to confirm Text on figure 1 Monday 3 Are you sure 4 No 5 Yes 6 Save 7 Modify Press the Escape key to leave this window The action is shown below the day the action is planned Te...

Page 65: ...one of the four programmed week schemes can be chosen Select Week Cycle from the main Week Timer menu list Text on figure 1 Week Timer 2 Week Action Schemes 3 Week Cycle 4 Status 5 Week Timer Inactive...

Page 66: ...3 Week Action Scheme 1 4 Week Action Scheme 2 5 Week Action Scheme 3 6 Modify Check the status of the Week Timer Use the Escape key on the controller to go back to the main Week Timer menu Select the...

Page 67: ...1 Week Timer 2 Week 3 Week Timer Inactive 4 Week 1 Press the Escape key on the controller to leave this window The status shows that week 1 is active Text on figure 1 Week Timer 2 Week Action Schemes...

Page 68: ...odify Text on figure 1 Week Timer 2 Week Action Schemes 3 Week Cycle 4 Status 5 Remaining Running Time This timer is used when the week timer is set and for certain reasons the dryer must continue wor...

Page 69: ...screen see Main screen Move the cursor to the action button Menu and press the enter key 2 following screen appears Using the scroll keys 1 move the cursor to the test icon see above section Menu ico...

Page 70: ...ervice menu Control panel 1 Scroll keys 2 Enter key 3 Escape key Menu icon Service Function To reset the service plans which are carried out To check when the next service plans are to be carried out...

Page 71: ...of running hours is 4000 hours upper row green and the programmed number of real time hours is 4380 hours which corresponds to six months second row blue This means that the controller will launch a s...

Page 72: ...ched a message will appear on the screen After carrying out the service actions related to the indicated levels the timers must be reset From the Service menu above select Service plan 3 and press Ent...

Page 73: ...time hours use the Scroll keys to select the desired action and press the Enter key 3 15 Converter menu Control panel 1 Scroll keys 2 Enter key 3 Escape key Menu icon Test Function To call up the spee...

Page 74: ...erant compressor appears 3 16 Protections menu Control panel 1 Scroll keys 2 Enter key 3 Escape key Menu icon Protections Function To call up and to reset the protections Before resetting a warning or...

Page 75: ...ppears Using the scroll keys 1 move the cursor to the protections icon see above section Menu icon Press the enter key 2 Following screen appears The screen shows a list of all shut down and shut down...

Page 76: ...re Starting from the Main screen see Main screen Move the cursor to the Menu action button and press the enter key 2 Following screen appears Using the scroll keys 1 move the cursor to the Extra icon...

Page 77: ...allows to consult certain data and settings via a PC instead of via the display of the controller Getting started Make sure you are logged in as administrator Use the internal network card from your...

Page 78: ...tion 1 which is connected to the controller Click with the right button and select properties 1 Use the checkbox Internet Protocol TCP IP 1 see picture To avoid conflicts de select other properties if...

Page 79: ...Instruction Book 9828 0934 73 79 Use the following settings IP Address 192 168 100 200 Subnetmask 255 255 255 0 Click OK and close network connections...

Page 80: ...nternal web server When using Opera or Firefox a redirect page opens Click on the hyperlink to connect to the download server from Microsoft to download the latest version of Internet Explorer and ins...

Page 81: ...se that you already added two IP addresses 192 168 100 1 and 192 168 100 2 Now you add 192 168 100 100 and separate the 3 IP addresses by putting semicolons between them 1 see picture Click OK 2 to cl...

Page 82: ...om the navigation menu Counters give an overview of all actual counters from controller and dryer Info status the machine status is always shown on the web interface Digital inputs gives an overview o...

Page 83: ...Instruction Book 9828 0934 73 83 4 Installation 4 1 Dimension drawings Dimension drawings Dimension drawing of air cooled QED 650 ES 310 QPVS 650 ES 310 VSD imperial units...

Page 84: ...Instruction Book 84 9828 0934 73 Dimension drawing of air cooled QED 650 ES 310 QPVS 650 ES 310 VSD metric units...

Page 85: ...Instruction Book 9828 0934 73 85 Dimension drawing of water cooled QED 650 ES 310 QPVS 650 ES 310 VSD metric units...

Page 86: ...Instruction Book 86 9828 0934 73 Dimension drawing of water cooled QED 650 ES 310 QPVS 650 ES 310 VSD imperial units...

Page 87: ...Instruction Book 9828 0934 73 87 Dimension drawing of air cooled QED 850 ES 410 QPVS 850 ES 410 VSD QPVS 1050 ES 510 VSD imperial units...

Page 88: ...Instruction Book 88 9828 0934 73 Dimension drawing of air cooled QED 850 ES 410 QPVS 850 ES 410 VSD QPVS 1050 ES 510 VSD metric units...

Page 89: ...Instruction Book 9828 0934 73 89 Dimension drawing of air cooled QED 1050 ES 510 imperial units...

Page 90: ...Instruction Book 90 9828 0934 73 Dimension drawing of air cooled QED 1050 ES 510 metric units...

Page 91: ...Instruction Book 9828 0934 73 91 Dimension drawing of water cooled QED 850 ES 410 QPVS 850 ES 410 VSD QPVS 1050 ES 510 VSD QED 1050 ES 510 imperial units...

Page 92: ...Instruction Book 92 9828 0934 73 Dimension drawing of water cooled QED 850 ES 410 QPVS 850 ES 410 VSD QPVS 1050 ES 510 VSD QED 1050 ES 510 metric units...

Page 93: ...Electrical connection cable gland M25 3 ISO7 R3 or 3 NPT 4 Cooling air out 5 Cooling air in 6 Net mass approx 7 Compressed air inlet 8 Compressed air outlet 9 Air cooled dryer type 10 Ambient 11 Maxi...

Page 94: ...Instruction Book 94 9828 0934 73 4 2 Installation proposal Example Installation proposal metric unit...

Page 95: ...Instruction Book 9828 0934 73 95 Installation proposal for water cooled metric unit Reference Description 1 Ventilation air inlet 2 Ventilation air outlet fan...

Page 96: ...er of 0 1 mg m3 0 1 ppm can be installed 2c A high efficiency filter may be installed downstream of the refrigerant dryer This filter traps particles down to 0 01 micron with a max oil carry over of 0...

Page 97: ...dryer free If necessary take action to avoid external influences wind draughts etc through the ventilation gratings of the dryer as they may disturb the cooling air flow For the reference of component...

Page 98: ...truction accessing the unit through the removable panels 4 4 Electrical cable size and fuses Important Local regulations remain applicable if they are stricter than the values proposed For 50 Hz dryer...

Page 99: ...A QPVS 1050 ES 510 VSD 400 V 3 x 16 A Electrical cable size Dryer Supply voltage Supply cable section recommended QED 650 ES 310 400 V 3 x 4 mm2 4 mm2 QPVS 650 ES 310 VSD 400 V 3 x 4 mm2 4 mm2 QED 85...

Page 100: ...y for 60 Hz units 2 Warning voltage 3 Cooling water outlet Only for water cooled dryers 4 Cooling water inlet Only for water cooled dryers 5 Maximum air inlet temperature of 70 C 158 F 6 Switch off an...

Page 101: ...least 10 minutes before starting the main supply to the dryer must be switched on to initialize the regulator and flow switch 2 Press start button 14 Three phase fix speed units are provided with a p...

Page 102: ...e dryer air inlet valve customer s installation Approx 5 minutes later open the dryer air outlet valve customer s installation Approx 10 minutes later the nominal dew point will be reached 5 4 During...

Page 103: ...Procedure for regulator as shown Procedure Step Action 1 Close dryer inlet and outlet valves customer s installation 2 Press stop button 13 The dryer stops Voltage on LED 8 remains lit Leave the volt...

Page 104: ...will also cause freezing of the eyes therefore safety glasses must be worn Refrigerant R410a is poisonous Do not inhale refrigerant vapors Check that the working area is adequately ventilated When rem...

Page 105: ...e Plan A Total Responsibility Plan Contact your Customer Center to arrange a tailor made service agreement This will ensure optimum operational efficiency minimize downtime and reduce the total life c...

Page 106: ...alfunction caused by the use of unauthorized parts is not covered by Warranty or Product Liability Apply all relevant Safety precautions Before carrying out any maintenance or repairs on the dryer sto...

Page 107: ...or Ambient temperature too high Check and correct if necessary draw cooling air via a duct from a cooler place or relocate dryer Condenser externally clogged Clean condenser Compressor stops or does n...

Page 108: ...compressor discharge temperature too high Too high load Reduce air flow Shortage of refrigerant Have circuit checked for leaks and recharged 7 1 3 Faults and remedies converter Only for VSD models Fa...

Page 109: ...30 Earth leakage Drive has detected load unbalance typically due to earth fault in motor or motor cable Check motor and motor cable for cabling errors Check motor and motor cable Check for an earth fa...

Page 110: ...n s Replace fan if faulty Make sure the front cover of the drive is in place and tightened Reboot the control unit 5090 STO hardware failure STO hardware diagnostics has detected hardware failure Repl...

Page 111: ...r 100 1 Referred to absolute pressure of 1 bar 14 5 psi and temperature of 20 C 68 F and measured according to ISO 7183 2 At other working conditions see AHB 2933 1870 00 Tab 17 Limitations Limitation...

Page 112: ...310 QED850 ES 410 QED1050 ES 510 Pressure dewpoint air outlet Ambient air temperature 25 C Compressed air inlet temperature 35 C C 3 3 3 Ambient air temperature 77 F Compressed air inlet temperature...

Page 113: ...l power input of fan s hp 0 5 0 8 1 1 Cooling air flow approx l s 1500 2200 3200 Cooling air flow approx cfm 3178 4662 6780 Heat dissipated by cooling medium flow approx Ambient air temperature 25 C C...

Page 114: ...mperature 104 F Compressed air inlet temperature 122 F F 55 4 51 8 42 8 Ambient air temperature 46 C Compressed air inlet temperature 56 C C 19 22 13 Ambient air temperature 115 F Compressed air inlet...

Page 115: ...mbient air temperature 77 F Compressed air inlet temperature 95 F hp 13 4 18 8 22 8 Ambient air temperature 30 C Compressed air inlet temperature 40 C kW 12 16 19 Ambient air temperature 86 F Compress...

Page 116: ...g water inlet of 40 C 104 F Unit At ambient temperature of C 25 30 35 40 At ambient temperature of F 77 86 95 104 Volume flow at dryer inlet under nominal conditions l s 310 310 310 310 Volume flow at...

Page 117: ...ing water inlet of 40 C 104 F Unit At ambient temperature of C 25 30 35 40 At ambient temperature of F 77 86 95 104 Volume flow at dryer inlet under nominal conditions l s 410 410 410 410 Volume flow...

Page 118: ...ssure dew point C 3 3 5 11 19 Total power consumption hp 4 2 4 2 4 2 4 2 4 3 Total power consumption kW 3 1 3 1 3 1 3 1 3 2 Cooling water flow approx cfm 0 4 0 6 0 6 0 6 0 6 Cooling water flow approx...

Page 119: ...41000 44400 51200 Heat dissipated by cooling water flow kW 11 11 12 13 15 QED 1050 ES 510 water cooled 50 Hz version Performance data with cooling water inlet of 25 C 77 F Unit At ambient temperature...

Page 120: ...flow approx l s 1 2 1 3 1 4 1 5 Cooling water flow approx cfm 2 54 2 75 2 97 3 18 Heat dissipated by cooling water flow approx kW 13 16 17 19 Heat dissipated by cooling water flow Btu hr 44369 54608 5...

Page 121: ...mperature of F 77 86 95 104 Volume flow at dryer inlet under nominal conditions l s 510 510 510 510 Volume flow at dryer inlet under nominal conditions cfm 1080 63 1080 63 1080 63 1080 63 Pressure dew...

Page 122: ...ing water flow approx kW 15 14 16 20 22 Cooling water flow at 25 C 77 F water inlet approx and a temperature difference of 10 C 18 F Performance data with cooling water inlet of 40 C 104 F Unit At amb...

Page 123: ...erature 104 F Compressed air inlet temperature 122 F F 77 0 77 0 77 0 Lowest dewpoint mode Ambient air temperature 25 C Compressed air inlet temperature 35 C C 3 3 3 Ambient air temperature 77 F Compr...

Page 124: ...et temperature 35 C kW 8 0 9 8 12 2 Ambient air temperature 77 F Compressed air inlet temperature 95 F Btu hr 27297 33439 41628 Ambient air temperature 40 C Compressed air inlet temperature 50 C kW 14...

Page 125: ...erature 35 C C 3 3 3 Ambient air temperature 77 F Compressed air inlet temperature 95 F F 37 4 37 4 37 4 Ambient air temperature 38 C Compressed air inlet temperature 38 C C 4 4 4 Ambient air temperat...

Page 126: ...ature 25 C Compressed air inlet temperature 35 C kW 8 0 9 8 12 2 Ambient air temperature 77 F Compressed air inlet temperature 95 F Btu hr 27297 33439 41628 Ambient air temperature 40 C Compressed air...

Page 127: ...air inlet temperature 122 F Cooling water inlet temperature 104 F F 68 68 68 Maximum saving mode Ambient air temperature 25 C Compressed air inlet temperature 35 C Cooling water inlet temperature 25 C...

Page 128: ...let temperature 77 F hp 1 82 2 68 3 31 Ambient air temperature 40 C Compressed air inlet temperature 50 C Cooling water inlet temperature 40 C kW 2 47 3 19 3 5 Ambient air temperature 104 F Compressed...

Page 129: ...bient air temperature 77 F Compressed air inlet temperature 95 F Cooling water inlet temperature 77 F cfm 0 42 0 64 0 85 Ambient air temperature 40 C Compressed air inlet temperature 50 C Cooling wate...

Page 130: ...emperature 35 C Cooling water inlet temperature 25 C kW 7 5 9 6 11 9 Ambient air temperature 77 F Compressed air inlet temperature 95 F Cooling water inlet temperature 77 F Btu hr 25591 32757 40605 Am...

Page 131: ...re 122 F Cooling water inlet temperature 104 F Btu hr 48794 63125 71314 Refrigerant gas and global warming potential The refrigerant gas for the dryer is R410A and the global warming potential is 2088...

Page 132: ...ir cooled 218 481 QED650 QPVS650 ES 310 ES 310 VSD water cooled 200 441 QED850 QPVS850 ES 410 ES 410 VSD air cooled 240 529 QED850 QPVS850 ES 410 ES 410 VSD water cooled 245 540 QED1050 QPVS1050 ES 51...

Page 133: ...bject to 2014 68 EU Pressure Equipment Directive Components subject to 2014 68 EU Pressure Equipment Directive greater than or equal to category II Description PED Class Compressor II Heat exchanger I...

Page 134: ...02 2021 No 9828 0934 73 Ed 00...

Reviews: