background image

4300 ACT Wood Stove Series

Page 22

250-7061C    December 10, 2004

R

OPACITY

This is the measure of how cleanly your stove is burning.  Opacity is measured in percent; 100% opacity is when an object 

is totally obscured by the smoke column from a chimney, and 0% opacity means that no smoke column can be seen.  As you 

become familiar with your stove, you should periodically check the opacity.  This will allow you to know how to burn your stove 

as nearly smoke-free as possible (goal of 0% opacity).  

BURN RATES

• 

STARTING FIRE:  

Open (push in) both controls fully.  After a wood load has been burning for 5 to 15 minutes (longer for very 

large pieces) close the Start-Up Air Control by pulling it out (to the right of the stove).  

• 

HIGH: 

 Leave the Primary Air Control fully open (center of stove under the ashcatcher).  It is important to do this when reloading 

the stove.  Failure to do this could result in excessive emissions (opacity).

After a wood load has been burning for 5 to 15 minutes on High to achieve the following burn rates 

set the controls as listed below:

• 

MEDIUM HIGH:

  Close the Primary Air Control to 1-1/4” to 2-1/2” (32-64mm) open,  Start-Up Air is closed.

• 

MEDIUM LOW

: Close the Primary Air Control  to 1” - 1-1/4” (25-32mm) open.  Start-Up Air is closed.

• 

LOW:

  Gradually close down the Primary Air Control, making sure to maintain flames in the stove. (Start-Up Air is closed.)  It is 

very important to maintain flames in your stove during the first few hours of a low burn to avoid excessive air pollution.

BLOWER OPERATING INSTRUCTIONS

(

See blower installation instructions on page 18)

If your Quadra-Fire wood stove is equipped with an optional blower, you should follow these guidelines:
1. 

Initial (cold) start-up:

  Leave blower off until your stove is hot and a good coalbed is established.  The blower may be 

turned on approximately 15 minutes after loading the stove with fuel.

2. 

High burn setting: 

 The blower may be left on throughout the burn.

3. 

Medium Low or Medium-High burn setting:

  The blower should be left off until a good burn is established, then turned 

on at a medium or high rate.

4. 

Low burn setting

:  The blower tends to cool off the stove.  If you are using wet wood or a very low burn setting, leave 

blower off until the burn is well established.  Then, if you wish, turn the blower on at a lower rate.  Too high a blower setting 

with a low burn rate may adversely affect emissions.

5.  The blower is equipped with a speed control.  The highest blower speed is obtained by turning the speed control to“ON” and 

then adjusting counterclockwise towards “OFF” as far as possible without turning the blower off.  For a low blower speed, 

turn the control knob clockwise as far as possible.

OPERATING INSTRUCTIONS (Cont’d)

CAUTION:  DO NOT STORE WOOD CLOSER THAN THE REQUIRED CLEARANCES TO COMBUSTIBLE OF THE STOVE OR 

WITHIN THE SPACE REQUIRED FOR LOADING AND ASH REMOVAL

.

WOOD SELECTION AND STORAGE

Burn only dry seasoned wood.  Store wood under cover, out of the rain and snow.    Dry and well-seasoned wood will not only 

minimize the chance of creosote formation, but will give you the most efficient fire.  Even dry wood contains at least 15% moisture 

by weight, and should be burned hot enough to keep the chimney hot for as long as it takes to dry the wood out - about one hour.  

It is a waste of energy to burn unseasoned wood of any kind.
Dead  wood  lying  on  the  forest  floor  should  be  considered  wet,  and  requires  full  seasoning  time.    Standing  dead  wood  can 

be  considered  to  be  about  two-thirds  seasoned.   To  tell  if  wood  is  dry  enough  to  burn,  check  the  ends  of  the  logs.    If  there 

are  cracks  radiating  in  all  directions  from  the  center,  it  is  dry.    If  your  wood  sizzles  in  the  fire,  even  though  the  surface  is 

dry, it may not be fully cured.  
Splitting wood before it is stored reduces drying time.  Wood should be stacked so that both ends of each piece are exposed to 

air, since more drying occurs through the cut ends than the sides.  This is true even with wood that has been split.  Store wood 

under cover, such as in a shed, or covered with a tarp, plastic, tar paper, sheets of scrap plywood, etc., as uncovered wood can 

absorb water from rain or snow, delaying the seasoning process.

Summary of Contents for 4300 Series

Page 1: ...owing has stopped OVERFIRING VOIDS YOUR WARRANTY 4 Cool ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE...

Page 2: ...are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold and nickel surfaces are hand finished for lasting beauty and enjoyment Our pledge to quality is completed...

Page 3: ...Dimensions 5 6 Locating Your Stove 6 Vent Speci cations 6 Clearances to Combustibles 7 Floor Protection 8 9 Alternate Materials Worksheet 9 INSTALLATION METHODS Chimney Height Draft 2 10 3 Rule 10 Flu...

Page 4: ...the chimney support base firestop as appropriate attic insulation shield insulated tee etc are necessary to assure a safe chimney installation Use only components manufactured for the chimney Chimney...

Page 5: ...mm 4 3 16 106mm 25 3 16 640mm 4300 STEP TOP UNI BODY PEDESTAL MODEL 4300 STEP TOP UNI BODY LEG MODEL 26 1 2 673mm 34 1 4 870mm 10 1 2 267mm 15 0 381mm 4 3 16 106mm 25 3 16 640mm 25 3 16 640mm 8 9 16 2...

Page 6: ...maintain the designated air space clearance around the chimney This space around a chimney is necessary to allow natural heat removal from the area Insulation in this space will cause a heat buildup...

Page 7: ...el INSTALLATION 90 Elbow Off Top of Stove Through Backwall DOUBLE WALL PIPE Flat Top Model Step Top Model INSTALLATION ALCOVE Six inch 6 152mm diameter listed Double Wall air insulated connector pipe...

Page 8: ...from the sides and rear of the stove See exception below EXCEPTION Non combustile oor protection must extend beneath the ue pipe when installed with horizontal venting and extend 2 51mm beyond each si...

Page 9: ...ormula in step 1 to convert values not expressed as R ii For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the system is greater than the R value...

Page 10: ...structure that is within 10 ft 305cm of the chimney measured horizontally See 2 10 3 Rule below These are safety requirements and are not meant to assure proper ue draft We recommend using a minimum t...

Page 11: ...iner 5 8 16mm Minimum or Equivalent Sill support Header Wood Stud 2 51mm Clearance from chimney wall Fireclay liner 5 8 16mm Minimum or Equivalent The ue should be checked to determine that it is not...

Page 12: ...speci ed by its manufacturer It may be necessary to cut the wall studs and install a header and a sill frame to maintain the wall support The hole in the chimney must have at least an 8 203mm diamete...

Page 13: ...nst the chimney Install the trim collar on the outside of the opening Check to make sure there is a 1 25mm air space between the connector and the chimney section During installation be certain that a...

Page 14: ...may ignite the ceiling joists The other method is to install an exterior chimney that runs up the outside of the residence Figure 14B This method of installation requires at a minimum a wall pass thr...

Page 15: ...Canada this appliance must be connected to a 6 152mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS Floor protection referenced on pages 8 9 must be followed 8 U...

Page 16: ...below 6 Swing open ash removal door and replace ash drawer with the overhanging lip facing toward you 7 Close ash removal door securely ARS OPERATING AND CLEANING FIGURE 16A 4 Using a rubber mallet i...

Page 17: ...Head socket or wrench from the adapter and save 5 Secure mounting brackets to the bottom of the stove with 1 4 20 Phillips screws These screws are located on the outer skin at the bottom rear of the...

Page 18: ...ower speed control for this unit is adjusted at the factory and normally does not require further adjustment 1 Remove the three bolts 1 4 20 Phillips Head on the outer skin at the bottom rear of stove...

Page 19: ...mm metal ex or rigid piping to directly connect outside air to the unit or into vented crawl space Do not put ex into a non vented crawl space Use the supplied termination cap with a rodent screen Sea...

Page 20: ...w burn rate you should close down the air to the point where you can still maintain some ame If the ames tend to go out the stove is set too low for your burning conditions The air control in the cent...

Page 21: ...will cure as your stove heats You will notice an odor and perhaps see some vapor rise from the stove surface this is normal We recommend that you open a window until the odor dissipates and paint is c...

Page 22: ...wer should be left off until a good burn is established then turned on at a medium or high rate 4 Low burn setting The blower tends to cool off the stove If you are using wet wood or a very low burn s...

Page 23: ...glass This air ow washes the glass helping to keep smoke from adhering to its surface When operated at a low burn rate less air will be owing over the glass and the smokey relatively cool condition o...

Page 24: ...0550 when ordering individual brick Please provide brick dimensions or copy this page and mark the desired brick and take it to your authorized dealer The Millennium Model does not accept the Ash Remo...

Page 25: ...e and ceramic blanket repeat steps 2 through 4 in reverse Be sure that the ber board baf e is pushed back fully and the blanket is down at The front of the blanket should be ush with the front of the...

Page 26: ...ndle Assembly 10 Leg Mounting Brackets 11 Legs Cast 12 Manifold Tubes 4 13 Oak Trim for Pedestal 2 14 Pedestal Base 1 11 2 3 4 5 6 7 8 9 10 12 13 14 EXPLODED VIEWS Item Part Name 1 Door Cast 2 Door Ha...

Page 27: ...sions needed see page 24 832 3401 Ceramic Blanket 1 thick eld cut to t size 17 x 19 831 1990 Component Pack includes paint gold spring handles and manual 472 5130 Door Handle Assembly 832 1680 Door Ro...

Page 28: ...4300 ACT Wood Stove Series Page 28 250 7061C December 10 2004 R NOTES...

Page 29: ...Page 29 250 7061C December 10 2004 4300 ACT Wood Stove Series R NOTES...

Page 30: ...4300 ACT Wood Stove Series Page 30 250 7061C December 10 2004 R Date of Service Performed By Description of Service Service and Maintenance Log...

Page 31: ...al accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installati...

Page 32: ...6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign pat...

Reviews: