background image

Page 11

 

250-7061C    December 10, 2004

4300 ACT Wood Stove Series

R

There are two separate and different parts to a flue system: the 

chimney connector and the chimney itself.

A. Single wall connector or stove pipe.  This must be at least 

24 gauge mild steel or 26 gauge blue steel.  The sections 

must be attached to the stove and to each other with the 

crimped (male) end pointing toward the stove.  

See Figure 

11A.

  All joints, including the connection at the stove collar, 

should be secured with three sheet metal screws.  Make 

sure to follow the minimum clearances to combustibles as 

set out on 

page 7

 of this manual.  Where passage through 

the wall, or partition of combustible construction is desired, 

the installation shall conform to CAN/CSA-B365 (Canada).

B.  Factory-built  listed  chimney  connector  (vented).   A  listed 

connector (vented) must be used when installing this unit 

in a mobile home.  The listed connectors must conform to 

each other to ensure a proper fit and seal.

FLUE 

GAS

 DIRECTION

CRIMPED 

END 

TOWARDS 

STOVE

FLUE SYSTEMS

WARNING!!    IF  INSTALLING  THIS  MODEL  TO A  MASONRY  CHIMNEY, ALWAYS  BE  SURE  THE  CHIMNEY  IS  IN  GOOD 

CONDITION AND THAT IT MEETS THE MINIMUM STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 

STANDARD 211.  A FACTORY BUILT CHIMNEY MUST BE 6” (152mm) UL103 HT.

THIS APPLIANCE IS MADE WITH A 6 INCH (152mm) DIAMETER CHIMNEY CONNECTOR AS THE FLUE COLLAR ON THE 

UNIT. CHANGING THE DIAMETER OF THE CHIMNEY CAN AFFECT DRAFT AND CAUSE POOR PERFORMANCE.  IT IS NOT 

RECOMMENDED TO USE OFFSETS OR ELBOWS AT ALTITUDES ABOVE 4000 FEET ABOVE SEA LEVEL OR WHEN THERE 

ARE OTHER FACTORS THAT AFFECT FLUE DRAFT.

FIGURE 11A - Chimney Connector

Thimble Assembly:

12" (305mm) of brick 

separation between 

clay liner and 

combustibles.

Fireclay liner 5/8" 

(16mm) Minimum 

or Equivalent.

Sill support

Header

Wood Stud 2" 

(51mm) 

Clearance 

from chimney 

wall

Fireclay liner 5/8" 

(16mm) Minimum 

or Equivalent.

The flue should be checked to determine that it is not too 

large for the stove. NFPA 211 allows the cross-sectional 

area of the flue to be no more than 3 times the cross-

sectional area of the flue collar of the stove (28 x 3 = 84 

square inches).  It is recommended that a chimney with 

a larger diameter than 6” (152mm) be relined, since the 

oversized flue can cause poor performance and contribute 

to the accumulation of creosote.  (

See page 10 

for more 

information about troubleshooting draft problems).  

CAUTION! DO NOT CONNECT THIS UNIT TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

When connecting the stove through a combustible wall to 

a masonry chimney, special methods are needed.  There 

are  several  ways  to  make  this  connection,  including 

the construction of a masonry thimble.  In Canada, the 

installation shall conform to CAN/CSA-B365.  Check with 

your local building authorities and/or consult the National 

Fire Protection Association (NFPA 211).  

Refer to Figure 

13B on page 13 and Figures 14A & 14B on page 14

MASONRY CHIMNEY

FIGURE 11B

Ensure that a masonry chimney meets the minimum standards 

of  the  National  Fire  Protection Association  (NFPA)  Standard 

211.  It  must  have  at  least  a  5/8"  (16mm)  fire  clay  liner  or  a 

listed chimney liner system. 

See Figure 11B

. Make sure there 

are  no  cracks,  loose  mortar  or  other  signs  of  deterioration 

and blockage.  It is best to have the chimney inspected by a 

professional, and be sure to have the chimney cleaned before 

the stove is installed and operated. 

MASONRY CHIMNEY (Cont’d)

For optimal performance, masonry chimneys used to vent this 

appliance  should  be  lined  with  a  6"  (152mm)  stainless  steel 

liner.  Installations into a clay flue without a stainless steel liner 

may reduce draw which affects performance, cause the glass 

to darken and produce excessive creosote.

Summary of Contents for 4300 Series

Page 1: ...owing has stopped OVERFIRING VOIDS YOUR WARRANTY 4 Cool ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE...

Page 2: ...are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold and nickel surfaces are hand finished for lasting beauty and enjoyment Our pledge to quality is completed...

Page 3: ...Dimensions 5 6 Locating Your Stove 6 Vent Speci cations 6 Clearances to Combustibles 7 Floor Protection 8 9 Alternate Materials Worksheet 9 INSTALLATION METHODS Chimney Height Draft 2 10 3 Rule 10 Flu...

Page 4: ...the chimney support base firestop as appropriate attic insulation shield insulated tee etc are necessary to assure a safe chimney installation Use only components manufactured for the chimney Chimney...

Page 5: ...mm 4 3 16 106mm 25 3 16 640mm 4300 STEP TOP UNI BODY PEDESTAL MODEL 4300 STEP TOP UNI BODY LEG MODEL 26 1 2 673mm 34 1 4 870mm 10 1 2 267mm 15 0 381mm 4 3 16 106mm 25 3 16 640mm 25 3 16 640mm 8 9 16 2...

Page 6: ...maintain the designated air space clearance around the chimney This space around a chimney is necessary to allow natural heat removal from the area Insulation in this space will cause a heat buildup...

Page 7: ...el INSTALLATION 90 Elbow Off Top of Stove Through Backwall DOUBLE WALL PIPE Flat Top Model Step Top Model INSTALLATION ALCOVE Six inch 6 152mm diameter listed Double Wall air insulated connector pipe...

Page 8: ...from the sides and rear of the stove See exception below EXCEPTION Non combustile oor protection must extend beneath the ue pipe when installed with horizontal venting and extend 2 51mm beyond each si...

Page 9: ...ormula in step 1 to convert values not expressed as R ii For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the system is greater than the R value...

Page 10: ...structure that is within 10 ft 305cm of the chimney measured horizontally See 2 10 3 Rule below These are safety requirements and are not meant to assure proper ue draft We recommend using a minimum t...

Page 11: ...iner 5 8 16mm Minimum or Equivalent Sill support Header Wood Stud 2 51mm Clearance from chimney wall Fireclay liner 5 8 16mm Minimum or Equivalent The ue should be checked to determine that it is not...

Page 12: ...speci ed by its manufacturer It may be necessary to cut the wall studs and install a header and a sill frame to maintain the wall support The hole in the chimney must have at least an 8 203mm diamete...

Page 13: ...nst the chimney Install the trim collar on the outside of the opening Check to make sure there is a 1 25mm air space between the connector and the chimney section During installation be certain that a...

Page 14: ...may ignite the ceiling joists The other method is to install an exterior chimney that runs up the outside of the residence Figure 14B This method of installation requires at a minimum a wall pass thr...

Page 15: ...Canada this appliance must be connected to a 6 152mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS Floor protection referenced on pages 8 9 must be followed 8 U...

Page 16: ...below 6 Swing open ash removal door and replace ash drawer with the overhanging lip facing toward you 7 Close ash removal door securely ARS OPERATING AND CLEANING FIGURE 16A 4 Using a rubber mallet i...

Page 17: ...Head socket or wrench from the adapter and save 5 Secure mounting brackets to the bottom of the stove with 1 4 20 Phillips screws These screws are located on the outer skin at the bottom rear of the...

Page 18: ...ower speed control for this unit is adjusted at the factory and normally does not require further adjustment 1 Remove the three bolts 1 4 20 Phillips Head on the outer skin at the bottom rear of stove...

Page 19: ...mm metal ex or rigid piping to directly connect outside air to the unit or into vented crawl space Do not put ex into a non vented crawl space Use the supplied termination cap with a rodent screen Sea...

Page 20: ...w burn rate you should close down the air to the point where you can still maintain some ame If the ames tend to go out the stove is set too low for your burning conditions The air control in the cent...

Page 21: ...will cure as your stove heats You will notice an odor and perhaps see some vapor rise from the stove surface this is normal We recommend that you open a window until the odor dissipates and paint is c...

Page 22: ...wer should be left off until a good burn is established then turned on at a medium or high rate 4 Low burn setting The blower tends to cool off the stove If you are using wet wood or a very low burn s...

Page 23: ...glass This air ow washes the glass helping to keep smoke from adhering to its surface When operated at a low burn rate less air will be owing over the glass and the smokey relatively cool condition o...

Page 24: ...0550 when ordering individual brick Please provide brick dimensions or copy this page and mark the desired brick and take it to your authorized dealer The Millennium Model does not accept the Ash Remo...

Page 25: ...e and ceramic blanket repeat steps 2 through 4 in reverse Be sure that the ber board baf e is pushed back fully and the blanket is down at The front of the blanket should be ush with the front of the...

Page 26: ...ndle Assembly 10 Leg Mounting Brackets 11 Legs Cast 12 Manifold Tubes 4 13 Oak Trim for Pedestal 2 14 Pedestal Base 1 11 2 3 4 5 6 7 8 9 10 12 13 14 EXPLODED VIEWS Item Part Name 1 Door Cast 2 Door Ha...

Page 27: ...sions needed see page 24 832 3401 Ceramic Blanket 1 thick eld cut to t size 17 x 19 831 1990 Component Pack includes paint gold spring handles and manual 472 5130 Door Handle Assembly 832 1680 Door Ro...

Page 28: ...4300 ACT Wood Stove Series Page 28 250 7061C December 10 2004 R NOTES...

Page 29: ...Page 29 250 7061C December 10 2004 4300 ACT Wood Stove Series R NOTES...

Page 30: ...4300 ACT Wood Stove Series Page 30 250 7061C December 10 2004 R Date of Service Performed By Description of Service Service and Maintenance Log...

Page 31: ...al accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installati...

Page 32: ...6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign pat...

Reviews: