background image

4300 ACT Wood Stove Series

Page 14

250-7061C    December 10, 2004

R

*

*

Floor

Protector

Chimney 

Connector

Combustible

Ceiling

Combustible Wall

Insulated " T "

Flashing

Listed Cap

Maintain 2" (51mm) 

Clearance Through Eave

*

Listed 

Chimney Pipe
Chimney 

Connector

To Stove

Trim Collar 

on Inside 

Wall

Combustible Outside Wall

2" (51mm) 

Clearance

Listed Chimney

Insulated " T "

Wall Support

Wall Spacer on 

Outside Wall

*

Refer to Clearances to Combustibles

CONNECTION TO A METAL PRE-FABRICATED CHIMNEY

When a metal prefabricated chimney is used, 

the  manufacturer’s  installation  instructions 

must  be  followed  precisely.   You  must  also 

purchase (from the same manufacturer) and 

install the ceiling support package or wall pass-

through  and  “T”  section  package,  firestops 

(where needed), insulation shield, roof flashing, 

chimney  cap,  etc.    Maintain  the  proper 

clearance to the structure as recommended by 

the manufacturer.  This clearance is usually a 

minimum of 2” (51mm), although it may vary by 

manufacturer or for certain components.

There  are  basically  two  methods  of  metal 

chimney installation.  One method is to install 

the chimney inside the residence through the 

ceiling and the roof 

(Figure 14A

).  I

nstall an 

attic  insulation  shield  to  maintain  the  specified 

clearance  to  insulation.    Insulation  in  this  air 

space will cause a heat buildup which may ignite 

the ceiling joists.

The other method is to install 

an exterior chimney that runs up the outside 

of the residence 

(Figure 14B)

.  This method 

of  installation  requires  at  a  minimum  a  wall 

pass-through device, a wall support package, 

insulated  “T”  section  and  roof  flashing.   The 

components illustrated may not look exactly like 

the system you purchase, but they demonstrate 

the  basic  components  you  will  need  for  a 

proper and safe installation.

Combustible Wall

Floor 
Protector

Chimney 
Connector

Ceiling Support

Listed Chimney

Maintain 2" (51mm) 

Clearance

Listed Cap

Storm Collar

Flashing

*

*

*

 Refer to Clearances    

        to Combustibles

Combustible 
Ceiling 
Joists

Chimney 
Connector

To Stove

Ceiling 

Support

Specified 
Clearance

Attic 
Insulation 
Shield

Listed 
Chimney

FIGURE 14A - INTERIOR CHIMNEY

The  chimney  must  be  the  required  height 

above the roof or other obstruction for safety 

and  proper  draft  operation.   The  chimney 

must  be  a  minimum  of  3  ft.  (91cm)  higher 

than the highest point where it passes through 

the  roof,  and  at  least  2  ft.  (61cm)  higher 

than the highest part of the roof or structure 

that is within 10’ ft. (305cm) of the chimney, 

measured horizontally 

(2-10-3 Rule Figure 

on page 10).

FIGURE 14B -EXTERIOR CHIMNEY

In Canada when using a factory-built chimney, make sure it is safety listed, Type UL 103 HT CLASS "A" 

or conforming to CAN/ULC-S629, STANDARD FOR 650°C FACTORY-BUILT CHIMNEYS.

IMPORTANT!

Follow the manufacturer’s 

installation instructions 

and maintain the 

manufacturer’s specified 

clearance distances.

Summary of Contents for 4300 Series

Page 1: ...owing has stopped OVERFIRING VOIDS YOUR WARRANTY 4 Cool ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE...

Page 2: ...are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold and nickel surfaces are hand finished for lasting beauty and enjoyment Our pledge to quality is completed...

Page 3: ...Dimensions 5 6 Locating Your Stove 6 Vent Speci cations 6 Clearances to Combustibles 7 Floor Protection 8 9 Alternate Materials Worksheet 9 INSTALLATION METHODS Chimney Height Draft 2 10 3 Rule 10 Flu...

Page 4: ...the chimney support base firestop as appropriate attic insulation shield insulated tee etc are necessary to assure a safe chimney installation Use only components manufactured for the chimney Chimney...

Page 5: ...mm 4 3 16 106mm 25 3 16 640mm 4300 STEP TOP UNI BODY PEDESTAL MODEL 4300 STEP TOP UNI BODY LEG MODEL 26 1 2 673mm 34 1 4 870mm 10 1 2 267mm 15 0 381mm 4 3 16 106mm 25 3 16 640mm 25 3 16 640mm 8 9 16 2...

Page 6: ...maintain the designated air space clearance around the chimney This space around a chimney is necessary to allow natural heat removal from the area Insulation in this space will cause a heat buildup...

Page 7: ...el INSTALLATION 90 Elbow Off Top of Stove Through Backwall DOUBLE WALL PIPE Flat Top Model Step Top Model INSTALLATION ALCOVE Six inch 6 152mm diameter listed Double Wall air insulated connector pipe...

Page 8: ...from the sides and rear of the stove See exception below EXCEPTION Non combustile oor protection must extend beneath the ue pipe when installed with horizontal venting and extend 2 51mm beyond each si...

Page 9: ...ormula in step 1 to convert values not expressed as R ii For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the system is greater than the R value...

Page 10: ...structure that is within 10 ft 305cm of the chimney measured horizontally See 2 10 3 Rule below These are safety requirements and are not meant to assure proper ue draft We recommend using a minimum t...

Page 11: ...iner 5 8 16mm Minimum or Equivalent Sill support Header Wood Stud 2 51mm Clearance from chimney wall Fireclay liner 5 8 16mm Minimum or Equivalent The ue should be checked to determine that it is not...

Page 12: ...speci ed by its manufacturer It may be necessary to cut the wall studs and install a header and a sill frame to maintain the wall support The hole in the chimney must have at least an 8 203mm diamete...

Page 13: ...nst the chimney Install the trim collar on the outside of the opening Check to make sure there is a 1 25mm air space between the connector and the chimney section During installation be certain that a...

Page 14: ...may ignite the ceiling joists The other method is to install an exterior chimney that runs up the outside of the residence Figure 14B This method of installation requires at a minimum a wall pass thr...

Page 15: ...Canada this appliance must be connected to a 6 152mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS Floor protection referenced on pages 8 9 must be followed 8 U...

Page 16: ...below 6 Swing open ash removal door and replace ash drawer with the overhanging lip facing toward you 7 Close ash removal door securely ARS OPERATING AND CLEANING FIGURE 16A 4 Using a rubber mallet i...

Page 17: ...Head socket or wrench from the adapter and save 5 Secure mounting brackets to the bottom of the stove with 1 4 20 Phillips screws These screws are located on the outer skin at the bottom rear of the...

Page 18: ...ower speed control for this unit is adjusted at the factory and normally does not require further adjustment 1 Remove the three bolts 1 4 20 Phillips Head on the outer skin at the bottom rear of stove...

Page 19: ...mm metal ex or rigid piping to directly connect outside air to the unit or into vented crawl space Do not put ex into a non vented crawl space Use the supplied termination cap with a rodent screen Sea...

Page 20: ...w burn rate you should close down the air to the point where you can still maintain some ame If the ames tend to go out the stove is set too low for your burning conditions The air control in the cent...

Page 21: ...will cure as your stove heats You will notice an odor and perhaps see some vapor rise from the stove surface this is normal We recommend that you open a window until the odor dissipates and paint is c...

Page 22: ...wer should be left off until a good burn is established then turned on at a medium or high rate 4 Low burn setting The blower tends to cool off the stove If you are using wet wood or a very low burn s...

Page 23: ...glass This air ow washes the glass helping to keep smoke from adhering to its surface When operated at a low burn rate less air will be owing over the glass and the smokey relatively cool condition o...

Page 24: ...0550 when ordering individual brick Please provide brick dimensions or copy this page and mark the desired brick and take it to your authorized dealer The Millennium Model does not accept the Ash Remo...

Page 25: ...e and ceramic blanket repeat steps 2 through 4 in reverse Be sure that the ber board baf e is pushed back fully and the blanket is down at The front of the blanket should be ush with the front of the...

Page 26: ...ndle Assembly 10 Leg Mounting Brackets 11 Legs Cast 12 Manifold Tubes 4 13 Oak Trim for Pedestal 2 14 Pedestal Base 1 11 2 3 4 5 6 7 8 9 10 12 13 14 EXPLODED VIEWS Item Part Name 1 Door Cast 2 Door Ha...

Page 27: ...sions needed see page 24 832 3401 Ceramic Blanket 1 thick eld cut to t size 17 x 19 831 1990 Component Pack includes paint gold spring handles and manual 472 5130 Door Handle Assembly 832 1680 Door Ro...

Page 28: ...4300 ACT Wood Stove Series Page 28 250 7061C December 10 2004 R NOTES...

Page 29: ...Page 29 250 7061C December 10 2004 4300 ACT Wood Stove Series R NOTES...

Page 30: ...4300 ACT Wood Stove Series Page 30 250 7061C December 10 2004 R Date of Service Performed By Description of Service Service and Maintenance Log...

Page 31: ...al accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installati...

Page 32: ...6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign pat...

Reviews: