SECTION 4 – SYSTEM INSTALLATION
UL EX3830 ULC EX3830
PagE 4-30 REV. 06 2014-NOV-10
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
Flexible Conduit Splicing (Allowed on Pull Station
Installations Only) (Continued)
3. Tighten compression union nut onto union body, locking
flexible conduit insert in place. See Figure 4-70.
FIGURE 4-70
008050
4. Install strain relief body into compression union and tighten.
See Figure 4-71.
FIGURE 4-71
008051
5. Push flexible conduit into strain relief until it is approximately
1/16 in. (1.6 mm) from the bottom of the flexible conduit
insert, then tighten strain relief nut onto strain relief body.
See Figure 4-72.
FIGURE 4-72
008052
6. Starting on the opposite end of the compression union,
remove the nut. See Figure 4-73.
FIGURE 4-73
008053
7. Install strain relief nut, strain relief, and compression union
nut on remaining section of flexible conduit and install flexi-
ble conduit insert on wire rope. See Figure 4-74.
FIGURE 4-74
008054
8. Push wire rope completely through remaining section of
flexible conduit. See Figure 4-75.
FIGURE 4-75
008055