SECTION 2 – COMPONENTS
UL EX3830 ULC EX3830
PagE 2-4 REV. 06 2014-NOV-10
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
MODEL EN-S ENCLOSuRE
The Model EN-S Enclosure (Part No. 550966) is used for vertical
mounting of a single PCL-160, PCL-300 or PCL-460 when it is
used as a secondary agent cylinder in a system. Dimensions
are the same as the Model EN-MCU3 enclosure (see Figure
2-10). The EN-S has no control mechanism, and must be used
in conjunction with a Model EN-MCU3 enclosure or a Model
MCH3/ECH3 control head.
Note
: The PCL-600 cannot be
mounted in an EN-S enclosure.
16 gRAM CO2 CARTRIDgE
The 16 gram CO
2
Cartridge (Part No. 551059) is required to
pneumatically actuate the tank valve. The cartridge is installed in
the control head on top of the tank valves. The cartridge shipping
assembly contains six cartridges.
MODEL MB-P2 – CONTROL HEAD MOuNTINg BRACKET
The Model MB-P2 Mounting Bracket (Part No. 550853) must
be used to mount the Model MCH3, NMCH3, or ECH3 control
heads if the control head is not mounted directly on a cylinder
valve. See Figure 2-11.
FIguRE 2-11
002846PC
PNEuMATIC ACTuATINg CYLINDERS
Model PAC-10
The Model PaC-10 (Part No. 550104) is a pneumatic actuating
cylinder that can actuate a maximum of ten agent cylinders
simultaneously. The Model PaC-10 includes a DOT 4Ba350
cylinder pressurized with dry nitrogen to 350 psig @ 70° F
(24.1 bar @ 21 °C), a brass valve with pressure gauge, and
a wall mounting bracket. a Model MCH3, NMCH3, or ECH3
control head must be purchased separately and connected to
the PaC-10 to open the valve. See Figure 2-12.
FIguRE 2-12
002847PC