SECTION 4 – SYSTEM INSTALLATION
UL EX3830 ULC EX3830
2014-NOV-10 REV. 06 PagE 4-27
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
Connecting Flexible Conduit to Pulley Elbows, Pulley
Tees, or Union Fittings (Continued)
7. Slide the flexible conduit into the strain relief until it is
approximately 1/16 in. (1.6 mm) from the bottom of the flex-
ible conduit insert. See Figure 4-55.
SLIDE FLEXIBLE CONDUIT
aPPROXIMaTELY 1/16 IN.
(1.6 mm) FROM BOTTOM OF
FLEXIBLE CONDUIT INSERT
FIGURE 4-55
008001
8. Tighten the strain relief nut onto the strain relief. See Figure
4-56.
TIgHTEN STRaIN
RELIEF NUT
FIGURE 4-56
008002
9. Complete the same procedures on the other end of the
conduit fitting as described in Step 1 through Step 8 above.
Installing Flexible Conduit Through a Conduit Offset
1.
Starting at the PYRO-CHEM control head, connect
the conduit connector using the supplied nut. Use only
PYRO-CHEM Conduit Fittings (Part No. 55813). See Figure
4-57.
FIGURE 4-57
008068
2. Install Conduit Offset (Part No. 79825) into conduit connec-
tor and tighten nut. See Figure 4-58.
FIGURE 4-58
008069
3. Install compression union to opposite end of conduit offset.
Tighten securely. See Figure 4-59.
FIGURE 4-59
008040