SECTION 4 – SYSTEM INSTALLATION
UL EX3830 ULC EX3830
PagE 4-24 REV. 06 2014-NOV-10
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
FLEXIBLE CONDUIT INSTALLATION (Continued)
Installation Instructions
Note:
Do not add any type of lubricants inside or on the flexible
conduit. Make certain stainless steel wire rope is clean and
debris-free.
The flexible conduit should be routed along the same path that
EMT conduit would normally be run. Stainless steel wire rope
should be routed through the flexible conduit as it is in EMT
conduit.
CAUTION
Flexible conduit must not be located within 6 in. (152 mm) of
the hood or in areas exceeding 130 °F (54 °C). also, do not
route flexible conduit in areas where conduit can be crushed,
pinched, or broken.
Flexible conduit can be used to connect a PYRO-CHEM control
head to a remote pull station or mechanical gas valves.
Before starting the system installation, take a few minutes to
plan the layout of the system. This will minimize the amount of
components needed to complete the installation. Once the path
of the flexible conduit has been determined, verify that the layout
does not exceed the design requirements.
Connecting the Flexible Conduit to the PYRO-CHEM
Control Head, Electrical Box, Pull Station, or Mechanical
Gas Valve
1. Layout the flexible conduit and secure it in place.
Note:
If
inner liner is crimped, turn a drywall screw into the end to
open it. See Figure 4-39.
IF SLIgHTLY CRIMPED,
TURN IN DRYWaLL
SCREW TO OPEN
FIGURE 4-39
007985
2. Starting at the PYRO-CHEM control head, connect the
conduit connector using the supplied nut. Use only PYRO-
CHEM Conduit Fittings (Part No. 55813). See Figure 4-40.
FIGURE 4-40
008068
3. Unscrew the nut from the EMT conduit connector and
remove the compression ring. Discard ring. See Figure
4-41.
NUT
DISCaRD
RINg
FIGURE 4-41
008070
4. Thread the stainless steel wire rope through the EMT
conduit connector and flexible conduit insert. Make certain
thread in flexible conduit insert is facing out toward end of
connector. See Figure 4-42.
FLEXIBLE
CONDUIT
INSERT
THREaDS
MUST FaCE
OUT
FIGURE 4-42
008071