ST Series User’s Manual
3-10
3.2.3
Grounding
(a) Exclusive Grounding (BEST)
*1
•
Connect the FG terminal found at the Power Plug to
an exclusive ground. [diagram (a)].
(b) Common Grounding (OK)
*1
•
If exclusive grounding is not possible, use a common
connection point. [diagram (b)]
Do not use common grounding, since it can lead to an accident or machine breakdown.
• When connecting an FG ground wire to the Power Plug's FG terminal, be sure to
create an exclusive ground. Check that the grounding resistance is less than
100
Ω
.
• Inside the ST400-AG41-24V/ST401-AG41-24V/ST402-AG41-24V/ST403-AG41-
24V unit, the SG (Signal Ground) and FG (Frame Ground) terminal are con-
nected to each other.
• When connecting the SG line to another device, be sure that the design of the
system/connection does not produce a shorting loop.
• The grounding wire should have a cross sectional area greater than 2mm
2
.
Create the connection point as close to the ST unit as possible, and make the
wire as short, as possible. When using a long grounding wire, replace the thin
wire with a thicker wire, and place it in a duct.
*1
Use a grounding resistance of less than 100
Ω
and a 2mm
2
or greater thickness wire, or your country’s
applicable standard. For details, contact your local GP distributor.
•
If the equipment does not function properly when grounded, disconnect the ground wire from
the FG terminal.
ST Unit
Other
Equipment
ST
Other
Equipment
ST
Other
Equipment
Summary of Contents for Pro-face ST Series
Page 1: ...User Manual ST Series...
Page 13: ...12 Memo...
Page 18: ...1 1 1 Introduction 1 1 Prior to Operating the ST 1 2 System Design 1 3 Accessories...
Page 54: ...4 1 4 Data Transfer 4 1 Serial Data Transfer 4 2 Ethernet Data Transfer...
Page 61: ...ST Series User s Manual 4 8 Memo...
Page 123: ...ST Series User s Manual 7 24 Memo...
Page 124: ...8 1 8 Maintenance 8 1 Regular Cleaning 8 2 Periodic Check Points 8 3 Changing the Backlight...