Chapter 2 Specifications
2-3
Structural
• When using any of the PL’s optional devices, be sure to check that device’s
specifications for any special conditions or cautions that may apply to its use.
• As a Hard Disk has a lifetime, it might be broken during operation. To prepare an
expected Hard Disk error, we recommend you take backup the data you need or
keep an alternate Hard Disk to exchange.
• It may cause a fatal error that the Hard Disk is used in a high temperature and
high moisture environment. We recommend that an appropriate environment be
29°C in Wet-bulb temperature (Maximum). This temperature, for example, is
equal to 64%RH (Relative Humidity) at 35°C, or 44%RH at 40°C.
Item
PL-6930
PL-6931
In
st
al
lation
Grounding
Grounding resistance of 100
Ω
, 2mm
2
or thicker wire, or your
country’s applicable standard. (Same for FG and SG terminals)
Structure
Rating
*1
: Equivalent to IP65f (Only not using Front USB)
figuration: Built-in type
Installation method: Embedding
*1
The front face of the PL unit, installed in a solid panel, has been tested using conditions equiv-
alent to the standards shown in the specification. Even though the PL unit’s level of resistance
is equivalent to these standards, oils that should have no effect on the PL can possibly harm
the unit. This can occur in areas where either vaporized oils are present, or where low viscos-
ity cutting oils are allowed to adhere to the unit for long periods of time. If the PL’s front face
protection sheet becomes peeled off, these conditions can lead to the ingress of oil into the PL
and separate protection measures are suggested. Also, if non-approved oils are present, it may
cause deformation or corrosion of the front panel’s plastic cover. Therefore, prior to installing
the PL be sure to confirm the type of conditions that will be present in the PL’s operating en-
vironment.
If the installation gasket is used for a long period of time, or if the unit and its gasket are re-
moved from the panel, the original level of the protection cannot be guaranteed. To maintain
the original protection level, be sure to replace the installation gasket regularly.
Cooling Method
Model without FAN (T41) : Natural air circulation
Model attached FAN (T42) : Forced cooling by fan
Weight
Approx. 9.5kg [20.9lb]
Approx. 8.5kg [18.7lb]
External
Dimensions
W346mm [13.62in.] × H287mm
[11.30in.] × D170mm [6.69in.]
W346mm [13.62in.] × H287mm
[11.30in.] × D123mm [4.84in.]