PL-6930 / PL-7930 Series User Manual
7-22
• When “Forced Shutdown” or “Forced Reboot” is written to the device address, the
system automatically shuts down/restarts the operation system without prompting
the confirmation for saving the data on current applications.
Take extra cautions when performing write operation in order to avoid accidental
data loss.
Value to be Written
Operation
Decimal Number
Hexadecimal Number
1
0001
Shutdown
2
0002
Reboot
257
0101
Forced Shutdown
258
0102
Forced Reboot