ConsoliDator Multi-Channel Controller
Instruction Manual
32
Multi-Channel High or Low
Alarm Modes
Multi-Channel High or Low modes
are used as an alarm triggered by a
set point common to the linked
channels.
Select [HIGH: Multi-Chan] from
Alarm Mode
options to turn relay on
(energize) when high set point is
reached by any linked channel, and
off when all linked channels are
below reset point.
Select [Low: Multi-Chan] from
Alarm
Mode
options to turn relay on
(energize) when low set point is
reached by any linked channel, and
off when all linked channels are
above reset point.
Alarm Setup: 1
Alarm Mode: HIGH: Multi-Chan
High Value: 160.0 GAL
Low Value: 8.0 GAL
Delay ON: 1.0 sec
Delay OFF: 0.5 sec
Link Channels:
1 2 3 4 5 6 7 8
EDIT
EXIT
ON:
Channel
Assign the relay to any analog or pulse input.
High Value
Enter high process variable set/reset point.
Low Value
Enter low process variable set/reset point.
Delay ON
Enter the delay between when the set point is reached and the
relay turns on (energizes.)
Delay OFF
Enter the delay between when the reset point is reached and the
relay turns off (de-energizes.)
Link Channels
Select the channels to link .