ConsoliDator Multi-Channel Controller
Instruction Manual
47
Table 2. Analog Input Channels Register Addresses
Address (offset from 40000)
Ch. 1 Ch. 2 Ch. 3 Ch. 4
Ch. 5* Ch. 6* Ch. 7* Ch. 8*
Description
Data Type
1
33
65
97
129
161
193
225
2
34
66
98
130
162
194
226
Engineering Value Floating Point
3
35
67
99
131
163
195
227
4
36
68
100
132
164
196
228
Max. Graph Value Floating Point
5
37
69
101
133
165
197
229
6
38
70
102
134
166
198
230
Min. Graph Value
Floating Point
7
39
71
103
135
167
199
231
8
40
72
104
136
168
200
232
High Value
Floating Point
9
41
73
105
137
169
201
233
10
42
74
106
138
170
202
234
High Value mA
Floating Point
11
43
75
107
139
171
203
235
12
44
76
108
140
172
204
236
Low Value
Floating Point
13
45
77
109
141
173
205
237
14
46
78
110
142
174
206
238
Low Value mA
Floating Point
15
47
79
111
143
175
207
239 Decimal Format
Byte
16
48
80
112
144
176
208
240 Ch. Online Flag
Byte
17
49
81
113
145
177
209
241 Ch. ID Char. 1
Byte
18
50
82
114
146
178
210
242 Ch. ID Char. 2
Byte
19
51
83
115
147
179
211
243 Ch. ID Char. 3
Byte
20
52
84
116
148
180
212
244 Ch. ID Char. 4
Byte
21
53
85
117
149
181
213
245 Ch. ID Char. 5
Byte
22
54
86
118
150
182
214
246 Ch. ID Char. 6
Byte
23
55
87
119
151
183
215
247 Ch. ID Char. 7
Byte
24
56
88
120
152
184
216
248 Ch. ID Char. 8
Byte
25
57
89
121
153
185
217
249 Ch. ID Char. 9
Byte
26
58
90
122
154
186
218
250 Ch. ID Char. 10
Byte
27
59
91
123
155
187
219
251 Units Character 1
Byte
28
60
92
124
156
188
220
252 Units Character 2
Byte
29
61
93
125
157
189
221
253 Units Character 3
Byte
1523 1547 1571 1595
1619
1643
1667
1691 Function Mode**
Byte
*Channels 5-8 only apply to ConsoliDator 8 (PD980 & PD981) models.
**Function Mode Byte Values:
Byte = 0: Linear
Byte = 16: Square Root
Byte = 32: Difference
Byte = 48: Summation
Byte = 64: Exponent
Byte = 80: Multi-Point
Byte = 96: Fixed Value
Byte = 112: Integration – Sec
Byte =128: Integration – Min
Byte = 144: Integration – Hour
Byte =160: Integration – Day