The parameters required for configuring
Retransmission
are grouped on PAGE-11. The configuration includes selecting the
Output type, Recorder Low & High settings etc. Refer Table 5.1 for parameter description & settings.
RETRANSMISSION PARAMETERS
Table 5.1
Parameter Description
Settings
(Default Value)
Min. to Max. Range
specified for the
selected Input Type
(Default : -200)
Select Output Signal type in accordance with the hardware
module fitted. Select 0-20 or 4-20 mA, if Current output module is
fitted. Select 0-5 or 0-10 V, if Voltage output module is fitted.
RECORDER OUTPUT TYPE
Set the minimum Process Value (
PV
) that shall correspond to the
minimum recorder output signal level (0mA or 4mA or 0V).
RECORDER LOW
Set the maximum Process Value (
PV
) that shall correspond to the
maximum recorder output signal level (20 mA or 10 V or 5 V).
RECORDER HIGH
(Default : 0 to 20 mA)
0 to 20 mA
4 to 20 mA
0 to 5 Volts
0 to 10 Volts
Min. to Max. Range
specified for the
selected Input Type
(Default : 1376)
User Manual
neuro 100
Section 5