14
The supervisory level responsibilities include exercising control over operator, making process related decisions and
controlling the availability of process data for remote use. The PAGE-13 parameters allow implementation of supervisory level
decisions. The Table 7.1 below lists supervisory parameters.
SUPERVISORY PARAMETERS
Table 7.1
User Manual
neuro 100
Parameter Description
Settings
(Default Value)
0 to 250
(Default : 0)
(Default : Serial Comm.)
None
Serial Comm.
Remote
Alarm Ack
(Default : 9.6)
4800
9600
19200
38400
57600
ALARM SP ADJUSTMENT
ON OPERATOR PAGE
Supervisory permission for Alarm setpoint adjustments on
Operator Page. Set to ‘Enable’ for permission.
PROCESS VALUE HIGH-LOW MONITORING
This parameter enables or disables the PV monitoring for
Min/Max values. Set to ‘Yes’ for enabling the feature.
This parameter allows protection against inadvertent resetting of
Min/Max values. That is, the reset command is executed only if the
operator sets the password that matches with this parameter
value.
PASSWORD FOR RESETTING
PV HIGH-LOW
Select the feature based on the hardware module fitted.
None
No hardware module fitted.
Serial Comm.
RS485 communication with host PC
Remote Alarm Ack
Connect potential-free switch for remote Alarm acknowledgment.
UTILITY OPTION SELECTION
BAUD RATE
Communication speed in ‘Bits per Second’. Set the value to match
with the host baud rate.
PARITY
One of the communication error trapping features. Select the data
packet parity as implemented by the host protocol.
(Default : Even)
None
Odd
Even
(Default : Disable)
Disable
Enable
(Default :No)
No
Yes
Section 7