23
The following precautions should be strictly observed while installing the indicator:
1.
The place of installation should be free of corrosive/combustible gases and electrically conductive pollution.
2.
Ensure that the place of installation is not subject to rapid ambient changes that can cause condensation. Also the Ambient
Temperature and Relative Humidity surrounding the indicator should not exceed the maximum specified for the proper
operation of the Indicator.
3.
The place of installation should be adequately protected against excessive electrostatic or electromagnetic interference.
4.
The Indicator should not be subject to direct vibration or shock.
5.
The Indicator should not be exposed to dust, salt air, direct sunlight or radiant heat.
OUTER DIMENSIONS
The Figure 10.1 shows the outer dimensions of the indicator.
MECHANICAL INSTALLATION
110mm
(4.33in)
10mm (0.39in)
Front View
Side View
Figure 10.1
PANEL CUTOUT AND RECOMMENDED MINIMUM SPACING
The Figure 10.2 shows the panel cutout requirements for a single Indicator and also the minimum spacing recommended if
several Indicators are required to be mounted on a single panel.
Panel Cutout
45 X 45 mm
-0, +0.5 mm
(1.77 X 1.77 in)
(-0, +0.02 in)
10mm (0.39in)
38mm (1.5in)
Figure 10.2
User Manual
neuro 100
Section 10
PPI
AL1
AL2
48mm
(1.89in)
48mm
(1.89in)
neuro 100