39
User Manual
neuro 100 96X96
If the Optional plug-in communication board is fitted, connect terminal 15 and 14 of the indicator to (+) and (-) terminals of the
Master device.
For reliable noise free communication, use a pair of twisted wires inside screened cable as shown in Figure 3.6.
The wire should have less than 100 ohms/km nominal DC resistance (Typically 24 AWG or thicker). Connect the terminating
resistor (Typically 100 to 150 ohm) at one end to improve noise immunity.
REMOTE ALARM ACKNOWLEDGMENT INPUTS
(Terminals : 14,15)
(Applicable if the Option plug-in module for Remote Alarm Acknowledge is fitted).
Use potential-free push button switch with normally Open contacts for the purpose of Alarm
Acknowledgment. Connect the switch across the terminals14 &15 as shown in figure 3.7.
Figure 3.7
14
15
Figure 3.6
SERIAL COMMUNICATION PORT
(Terminals : 14 , 15)
(Applicable if the Option plug-in module for RS485 Serial Port is fitted)
Terminating Resistor
Screened Cable
Twisted
Wire Pair
(100 to 150 Ohms)
15 (B-)
HOST
B-
B+
Master Device
Serial Comm.
Terminals
14 (B+)