Note 1: this item needs to be changed with [I / O setting] item, and it can be used only after the
setting is completed.
1.
In [temp. setting], press
+
+
2 sec at the same time,
shows [F-81] and
then entering password.
2. Press
,
shows [F-82],
lock the setting on
(Please see table 1 and 2.).
3. Press
,
shows [F-83],
customer can set the password on
to enter
[F-82].
4. Press
, back to
[F-81]
by cycle.
5. Press
2 sec, back to
[Temp. setting].
6. Parameters 7: [Lock Parameter]
Code
Name
Explanation
Value
Unit
Factory
setting
Range
F81
Lock parameter
Entering password
Enter the password for enter
into the locked layer.
3
0~9999
Factory password:3
F82
Lock layer
Choose the parameter layer
to lock.
0
0-2
Table 1 & 2
F83
Setting password
Set the password by entering
[LK-1]
3
0~9999
Enter the password in[F-81]
F22
GAI2 CH2
Magnification
Correction
Adjust the error value of wire to correct
magnification value.
1000
1~1000
F21.3
OFS3 CH3
Temp. Correction
Correct wire deviation V.S. deviation of actual
temp signal.
0.0
-
99.9~100.0
℃
/
℉
F22.3
GAI3 CH3
Magnification
Correction
Adjust the error value of wire to correct
magnification value.
1000
1~1000
F23
Display filter
Inhibit to be affected by the noise input signal.
5
0-250
F24
Remote control
Remote control for ON/OFF the controller
OFF
ON: open
OFF: close
F25
Current output
Lowest limit adjustment
Output power supply is set 0% for checking
current output by 4mA,
Current is too high: decrease the value
Current is too low: increase the value
22
0-100
MA
F26
Current output
Upper limit adjustment
Output power supply is set 100% for checking
current output by 20mA,
Current is too high: increase the value
Current is too low: decrease the value
27
0-100
MA