Parameter group
1. Parameters 4: [Temp. Parameter]
Code
Name
Explanation
Value
Unit
Factory
setting
Range
F-27
P - Heating
proportion
Setting temperature control proportion
0: on/off action
20.0
0~+999.9
F-28
I - Heating integration
time
Eliminate the difference of proportion control
Set 0:PD action
240
0~+9999
F-29
D - Heating
differentiation time
Prevent the stability increased from fluctuate
temperature
Set 0:PI action
60
0~+9999
F-30
PC - Cooling
proportion
According to heating, please set the cooling
proportion from 0 to 1000%.
1000 0~+9999
F-31
ARW - Limited
effective range
Prevent over adjustment from integral action
100
0~+100
F-32
No induction
Set no induction band of heating and cooling. If there is
only heating function, it should be on induction band
of ON/OFF
0.5
0~+20.0
℃
/
℉
F-33
HCYT - Heating cycle
time
Output cycle time
Relay: 20 sec
Voltage pulse: 2 sec
Current: 0 sec
20.0
0~+360.0
sec
F-34
CCYT - Cooling cycle
time
Eliminate the difference of proportion control
Set 0:PD action
20.0
0~+360.0
sec
2. Parameters 5:[Communication Parameter]
Code
Name
Explanation
Value
Unit
Factory setting
Range
F-35
Communication address
Setting communication address
1
0-250
F-36
Communication rate
0: 9600 bps 1: 19200 bps
2: 38400 bps 3: 57600 bps
2
0-3
bps
F-37
Interval time of reaction
When does machine react after
receiving correct command?
0
0-100
ms
F-38
Communication back up Communication back up(to EEP rom)
OFF
ON: save
OFF: not save
20