Chapter 5 Function parameter
91
Ch
ap
ter 5
F7.47 Awakens delay time
0.0s~6500.0s
0.0s
☆
F7.48 Dormancy frequency
0.00Hz~ awakens frequency (F7.46)
0.00Hz
☆
F7.49 Dormancy delay time
0.0s~6500.0s
0.0s
☆
F7.50
AI1 input voltage protection
lower limit
0.00V~F7.51
3.10V
☆
F7.51
AI1 input voltage
protection upper limit
F7.50~10.00V
6.80V
☆
When analog AI1 input is greater than F7.51, or when AI1 input is less than F7.50, the
inverter multi-functional DO will output "AI1 input overrun"signal, so as to indicate whether the
AI1 input voltage is within the set range or not.
F7.52
F7.53
Reserve
F7.54 Jog mode setting
Bits
Jog direction
002
☆
Forward
0
reverse
1
Determine the direction from the main
terminal
2
Ten bits
End running state by Jogging
Restore to the state before jogging
0
stop running
1
Hundred
bits
Acceleration/deceleration time after
stop jogging
Recover to the acceleration/deceleration
time before jogging
0
Keep the acceleration/deceleration time when
jogging
1
5-2-10.Fault and protection:F8.00-F8.35
Code
Parameter name
Setting range
Factory
setting
Change
limits
F8.00 Over-current stall gain
0~100
20
☆
F8.01
Over-current stall protection
current
100%~200%
-
☆
When the inverter output current reaches the set current stall protection current (F8.01), the
inverter reduces the output frequency in the acceleration or constant speed operation, while the
slow down speed, until the current is less than the current (F8.01).
Over-current stall gain is used for adjusting inhibition over-current capability during
ac/deceleration. The greater this value, the stronger inhibition over-current capability Under the
premise that the over-current does not occur, the best is the smaller gain setting.
For the small inertia load, the over-current stall gain should be small, otherwise which cause
the slower system dynamic response. For the big inertia load, the over-current stall gain should be
large, otherwise the poor inhibitory effect may cause over-current fault.
When the over-current stall gain is set to 0, the over-current stall function will be canceled.
F8.02 Motor over-load protection
Prohibit
0
1
☆
Allow
1
F8.03 Motor over-load protection gain 0.20~10.00
1.00
☆
F8.02 = 0: no motor overload protection function, there may be the risk of damage to the
motor due to overheating, it is recommended that the thermal relay is installed between the inverter
and the motor;
F8.02 = 1: the inverter will determine whether the motor is overloaded or not according to the
inverse time curve of motor overload protection. Inverse time curve of motor overload protection:
220% x (F8.03) x rated motor current, if this lasts for 1 second, the alarm of motor will be
prompted overload fault; 150% x (F8.03) × rated motor current, if this lasts for 60 seconds, the