Chapter 5 Function parameter
35
Ch
ap
ter 5
status selection
0: positive logic
;
1: anti-logic
Tens digit: Relay 1
Hundreds digit: Hundreds digit:
Undefined
Thousands digit: SPA
Ten thousands digit: Relay 2
126
F2.16 DA1 zero bias coefficient
-100.0% to +100.0%
0.0%
☆
127
F2.17 DA1 gain
-10.00 to +10.00
1.00
☆
128
F2.18 DA2 zero bias coefficient
-100.0% to +100.0%
20.0%
☆
129
F2.19 DA2 gain
-10.00 to +10.00
0.80
☆
5-1-5.F3Group - Start and stop control group
No. Code
Parameter name
Setting range
Factory
setting
Ch
ang
e
130
F3.00 Start-up mode
0: Direct startup
0
☆
131
F3.03 Start frequency
0.00Hz to 10.00Hz
0.00Hz
☆
132
F3.04
Hold time for start
frequency
0.0s to 100.0s
0.0s
★
133
F3.07 Stop mode
0: Deceleration parking 1: Free stop
0
☆
134
F3.08 DC Initial frequency
0.00Hz to F0.19 (maximum frequency)
0.00Hz
☆
135
F3.09 DC Waiting time
0.0s to 100.0s
0.0s
☆
136
F3.13 Ac/deceleration mode
0: Linear acceleration and deceleration
1:S curve acceleration and deceleration A
0
★
137
F3.14
Proportion of S curve
start-section
0.0% to (100.0%to F3.15)
30.0%
★
138
F3.15
Proportion of S curve
end-section
0.0% to (100.0% to F3.14)
30.0%
★
5-1-6.F4 Group - V/F control parameters
No. Code
Parameter name
Setting range
Factory
setting
Chang
e
139
F4.00 V/F curve setting
0 to11
0
★
140
F4.01 Torque boost
0.0%(Automatic torque boost)0.1 to 30%
0.0%
★
141
F4.02
Torque boost cut-off
frequency
0.00Hz to F0.19(maximum frequency)
15.00Hz
★
142
F4.03
MultipointV/F
frequency point 1
0.00Hz to F4.05
0.00Hz
★
143
F4.04
Multipoint V/F
voltage point 1
0.0% to 100.0%
0.0%
★
144
F4.05
Multipoint V/F
frequency point 2
F4.03 to F4.07
0.00Hz
★
145
F4.06
Multipoint V/F
voltage point 2
0.0% to 100.0%
0.0%
★
146
F4.07 Multipoint V/F
F4.05 to b0.04 (rated motor frequency)
0.00Hz
★