Chapter 5 Function parameter
49
Ch
ap
ter 5
switching conditions
1: switching via terminals
2: automatically switching according to
deviation.
395
E2.20
PID parameter
switching deviation 1
0.0% to E2.21
20.0%
☆
396
E2.21
PID parameter
switching deviation 2
E2.20 to 100.0%
80.0%
☆
397
E2.22 PID integral properties
Units digit: integral separation
0: Invalid; 1: Valid
Tens digit: whether stop integration
when output reaches limit
0: continue; 1: stop
00
☆
398
E2.23 PID initial value
0.0% to 100.0%
0.0%
☆
399
E2.24
PID initial value hold
time
0.00s to 360.00s
0.00s
☆
400
E2.25
Maximum deviation of
twice outputs(forward)
0.00% to 100.00%
1.00%
☆
401
E2.26
Maximum deviation of
twice outputs(backward)
0.00% to 100.00%
1.00%
☆
402
E2.27
Computing status after
PID stop
0: stop without computing
1: stop with computing
1
☆
403
E2.28 reserved
404
E2.29
PID automatic decrease
frequency selection
0
:
invalid
;
1
:
valid
1
☆
405
E2.30 PID stop frequency
0.00Hz~maximum frequency(F0.19)
25
☆
406
E2.31 PID checking time
0s~3600s
10
☆
407
E2.32 PID checking times
10~500
20
☆
5-1-17.E3 Group – Virtual DI
、
Virtual DO
No.
Code
Parameter name
Setting range
Factory
setting
Cha
nge
408
E3.00
Virtual VDI1 terminal
function selection
0 to 50
0
★
409
E3.01
Virtual VDI2 terminal
function selection
0 to 50
0
★
410
E3.02
Virtual VDI3 terminal
function selection
0 to 50
0
★
411
E3.03
Virtual VDI4 terminal
function selection
0 to 50
0
★
412
E3.04
Virtual VDI5 terminal
function selection
0 to 50
0
★
413
E3.05
Virtual VDI terminal
status set
Units digit:Virtual VDI1
Tens digit:Virtual VDI2
Hundreds digit:Virtual VDI3
Thousands digit:Virtual VDI4
Tens of thousands:Virtual VDI5
00000 ★