Chapter 5 Function parameter
90
Ch
ap
ter 5
When the inverter's output current is more than or overrun the detection point and lasts for
longer than the delay time of software over-current point detection, the inverter's multi-function
DO will output ON signal.
F7.36 Random arrivals current 1
0.0%~300.0%(rated motor current)
-100%
☆
F7.37 Random arrivals current 1 width
0.0%~300.0%(rated motor current)
0.0%
☆
F7.38 Random arrivals current 2
0.0%~300.0%(rated motor current)
-100%
☆
F7.39 Random arrivals current 2 width
0.0%~300.0%(rated motor current)
0.0%
☆
When the inverter's output current randomly reaches the range of the current detection
width(positive or negative), the inverter multi-function DO will output ON signal.
PI500-E provides two group of sets of parameter for Randomly Reaches Current and
Detection Width, the figure is the functional diagram.
Random arrivals current
Time(t)
Output Current
Random arrivals current
detection signal DO orrelay
ON
OFF
ON
OFF
OFF
Random arrivals current width
ON
Random arrivals current width
Figure5-23:Schematic diagram of random arrivals current detection
F7.40 Module temperature arrival
0
℃
~100
℃
75
℃
☆
When the inverter radiator temperature reaches the temperature, the inverter multi-function
DO will output "Module Temperature Arrival" ON signal.
F7.41 Cooling fan control
Fan running only when running
0
0
☆
Fan always running
1
Used to select the cooling fan mode, if you select 0, the fan will run when the inverter is
running, but in the stop state of inverter, if the radiator temperature is above 40 degrees, the fan
will run, otherwise the fan will not run. When select 1, when the fan will always running after
power-on.
F7.42 Timing function selection
Invalid
0
0
★
Valid
1
F7.43 Timing run time selection
F7.44 setting
0
0
★
AI1
1
AI2
2
Panel potentiometer
3
Analog input range 100% corresponds to F7.44
F7.44 Timing run time
0.0Min~6500.0Min
0.0Min
★
The group of parameters are used to complete the inverter timing run function.
If F7.42 timing function is active, the inverter starts as the timer starts, when the set timing
run time is reached, the inverter automatically shut down, at the same time the multi-function DO
will output ON signal.
Every time the inverter starts, the timer will time from 0, the remaining time can be viewed
by d0.20. The timing run time is set by F7.43, F7.44 in minute.
F7.45 Current running arrival time. 0.0Min~6500.0Min
0.0Min
★
When current running time reaches this time, the inverter multi-function digital DO will
output"Current Running Time Arrival "ON signal.
F7.46 Awakens frequency
Dormancy frequency (F7.48)~ to
maximum frequency (F0.19)
0.00Hz
☆