Chapter 5 Function parameter
38
No. Code
Parameter name
Setting range
Factory
default
Change
Reference
page
communication control
mode only)
3: No alarm and stop at
the selected mode (under
all control modes)
131.
F9.07
Transmission
response handling
0: Write operations
responded
1: Write operations not
responded
0
☆
75
5-1-12.FA Group - Torque control
No. Code
Parameter
name
Setting range
Factory
default
Change
Reference
page
132.
FA.00
Torque
setting mode
selection
0: Keyboard setting (FA.01)
1: Analog AI1 setting
2: Analog AI2 setting
3: Panel potentiometer
setting
4: Analog AI1+AI2 setting
5: Multi-segment torque
setting
6: Remote communications
setting
Note: Option 1 to 6, 100%
relative to two times of the
rated current of inverter
0
☆
75
133.
FA.01
Keyboard set
torque
-200.0% to 200.0% (rated
current of inverter)
50.0%
☆
76
5-1-13.Fb Group - Control optimization
No. Code
Parameter name
Setting range
Factory
default
Change
Reference
page
134.
Fb.00
Software overcurrent
point
4 to 2000A
Depends
on models
★
76
135.
Fb.01
Software undervoltage
point
0 to 500V
Depends
on models
★
76
136.
Fb.02
Software overvoltage
point
300 to 800V
Depends
on models
★
76
137.
Fb.03
Low-frequency
threshold point of
oscillation suppression
0 to 500
5
☆
76