Chapter 5 Function parameter
39
No. Code
Parameter name
Setting range
Factory
default
Change
Reference
page
138.
Fb.04
High-frequency
threshold point of
oscillation suppression
0 to 500
100
☆
76
139.
Fb.05
Amplitude limit value
of oscillation
suppression
0 to 10000
5000
☆
77
140.
Fb.06
Demarcation
frequency of high and
low frequency of
oscillation suppression
0.00Hz to F0.08
(maximum
output
frequency)
12.50Hz
☆
77
141.
Fb.07
Oscillation
suppression
0: valid
1: invalid
1
☆
77
142.
Fb.08 PWM selection
0: PWM mode 1
1: PWM mode 2
2: PWM mode 3
0
★
77
143.
Fb.09
Energy-saving
selection
0: OFF
1. Auto
0
★
77
144.
Fb.10 Deadband time
2 to 5
Depends
on models
★
77
5-1-14.E0 Group - Wobbulate control
No. Code Parameter name
Setting range
Factory
default
Change
Reference
page
145.
E0.00 Wobbulate range
0.0 to 100.0% (relative
to setting frequency)
0.0%
☆
78
146.
E0.01
Sudden jump
frequency range
0.0 to 50.0% (relative
to Wobbulate
amplitude)
0.0%
☆
78
147.
E0.02
Wobbulate rise
time
0.1 to 3600.0s
5.0 s
☆
78
148.
E0.03
Wobbulate fall
time
0.1 to 3600.0s
5.0 s
☆
78
5-1-15.E1 Group - Multi-speed control
No.
Code Parameter name
Setting range Factory default Change Reference page
149.
E1.00 Multi-speed 0
-100.0 to 100.0%
0.0%
☆
78
150.
E1.01 Multi-speed 1
-100.0 to 100.0%
0.0%
☆
78