Chapter 5 Function parameter
56
Code
Parameter name
Setting range
Factory
default
Change
SB1
SB3
K1
Running
direction
OFF
ON
Forward
Reverse
SB1
SB2
SB3
Stop button
Forward
button
Reverse
button
Three-wire control mode 1
Three-wire control mode 2
In
v
er
te
r
FWD
REV
COM
SB2
DIn
K1
SB1
In
v
er
te
r
FWD
REV
COM
SB2
DIn
F1.07
Change rate of terminal
UP/DOWN frequency
increment
0.01 to 50.00Hz/s
0.50Hz/
s
☆
When the terminal UP/DOWN is used to adjust the set frequency, the rate of frequency
change, i.e. frequency change amount per second.
F1.08 AI1 lower limit
0.00V to F1.10
0.00V
☆
F1.09 AI1 lower limit setting
-100.0% to 100.0%
0.0%
☆
F1.10 AI1 upper limit
F1.08 to 10.00V
10.00V
☆
F1.11 AI1 upper limit setting
-100.0% to 100.0%
100.0%
☆
F1.12 Filter time of AI1 input
0.00s to 10.00s
0.10s
☆
The above function code defines the relationship between analog input voltage and the
analog input, when the analog input voltage exceeds the maximum input or minimum
input, the maximum input or the minimum input will be used for calculation.
When the analog input is the current input, 0mA to 20mA current corresponds to 0V to
10V voltage.
In the different applications, the 100.0% of analog setting vary from the meaning of its
corresponding nominal value, please refer to the description of each application for
details.
对应频率
100%
10V
AI
20mA
0
-100%
Relationship diagram between analog reference and set amount
AI1 Input filter time: Adjust analog input sensitivity. if this value is increased
Corresponding
frequency