Chapter 5 Function parameter
73
Code
Parameter name
Setting range
Factory
default
Change
Number of automatic fault reset: when the inverter selects automatic fault reset, it is
used to set the number of times of automatic fault reset. When the times of the inverter
continuous reset exceed this value, the inverter fault standby, the manual intervention is
required.
Automatic fault reset interval setting: choose interval between fault occurrence and
automatic reset.
F8.09
Descending frequency
point of momentary
power failure
70.0 to 110.0% (standard bus
voltage)
80.0%
☆
F8.10
Frequency fall rate of
momentary power failure
0.00Hz/s to F0.08 (maximum
output frequency)
0.00Hz/s
☆
5-2-11.F9 Group - Communication parameter group
Code
Parameter name
Setting range
Factory
default
Change
F9.00
Communication baud
rate setting
1200bps
0
3
☆
2400bps
1
4800bps
2
9600bps
3
19200bps
4
38400bps
5
This parameter is used to set the data transfer rate between the host computer and the
inverter. Note: the baud rate must be set to the same for the host computer and the
inverter, otherwise communication can not be achieved. The larger baud rate, the faster
communication speed.
F9.01 Data bits parity settings
0: no parity (N, 8, 1) for RTU
1: even parity (E, 8, 1) for RTU
2: odd parity (O, 8, 1) for RTU
3: no parity (N, 8, 2) for RTU
4: even parity (E, 8, 2) for RTU
5: odd parity (O, 8, 2) for RTU
6: no parity (N, 7, 1) for ASCII
7: even parity (E, 7, 1) for
ASCII
8: odd parity (O, 7, 1) for
ASCII
9: no parity (N, 7, 2) for ASCII
1
☆