Chapter 3 Keyboard
20
b0.02: motor rated voltage b0.03: motor rated
current
b0.04: motor rated frequency b0.05: motor rated
speed
If the motor can completely disengage its load, please select 1 (asynchronous
motor parameter comprehensive auto tunning) for b0.11, and then press the RUN key on
the keyboard panel:
If the motor can NOT completely disengage its load, please select 2 (asynchronous
motor parameter static auto tunning) for b0.11, and then press the RUN key on the
keyboard panel, the inverter will automatically calculate the motor‟s following
parameters:
Motor
Selection
Parameters
Motor
b0.06: Asynchronous motor stator resistance
b0.07: Asynchronous motor rotor resistance
b0.08: Asynchronous motor stator and rotor
inductance
b0.09: Asynchronous motor stator and rotor
mutual inductance
b0.10: Asynchronous motor no-load current
Complete motor parameter auto tunning