background image

 

 

PBAT

NBAT

TO UPS BAT+

TO UPS BAT N

TO UPS BAT-

 

Battery wire connect schematic 

NOTE 1: 

Make sure that the wires are connected tightly with the terminals.   

NOTE 2: 

Please install the output breaker between the output terminal and the load, and the breaker should be 

qualified with leakage current protective function if necessary. 
6)

 

Put the terminal block cover back at the rear panel of the UPS. 

 

Warning: 

(Only for standard model) 

● Make sure the UPS is not turn on before the installation. The UPS should not be turned on during wiring 

connection. 

● Do not attempt to modify the standard model into the long-run model. Particularly, do not try to connect the 

standard  internal  battery  to  the  external  battery. The  battery  type and  voltage  may  be  different, if  you 

connect them together, it maybe cause the hazard of electric shock or fire! 

 

Warning:

 (Only for long-run model) 

● Make sure a DC breaker or other protective device between UPS and the external battery pack is installed. If 

not, please install it carefully. Switch off the battery breaker before installation. 

NOTE: 

Set the battery pack breaker in “OFF” position and then install the battery pack. 

●  Pay  highly  attention  to  the  rated  battery  voltage marked  on  the  rear  panel.  If  you  want  to  change  the 

numbers of the battery pack, please make sure you modify the setting simultaneously. The Connection with 

wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack 

is correct.   

● Pay highly attention to the polarity marking on external battery terminal block. And make sure the correct 

battery polarity is connected. Wrong connection may cause permanent damage of the UPS. 

● Make sure the protective earth ground wiring is correct. The wire current spec,    color, position, connection 

and conductance reliability should be checked carefully. 

● Make sure the utility input & output wire is correct. The wire current spec, color, position, connection and 

conductance  reliability  should  be  checked  carefully.  Make  sure  the  L/N  side  is  correct,  not  reverse  or 
short-circuited. 

2-4. UPS Installation for Parallel System 

If the UPS is only available for single operation, you may skip this section to the next. 
1)

 

Install and wires the UPS according to the section 2-3. 

2)

 

Connect the output wires of each UPS to an output breaker. 

3)

 

Connect all output breakers to a major output

 

breaker. Then this major output breaker will directly connect to 

the loads. 

4)

 

Common battery packs or independent battery packs are allowed. 

5)

 

Refer to the following wiring diagram: 

 

Summary of Contents for VFI 10KL CPG PF1 3/3

Page 1: ...PowerWalker VFI 10K 80K CPG PF1 3 3 Uninterruptible Power Supply System Version 1 0 1...

Page 2: ...E 26 5 2 MAINTENANCE 26 6 SPECIFICATIONS 27 Please comply with all warnings and operating instructions in this manual This equipment should only be installed serviced and maintained by qualified perso...

Page 3: ...n the final installation phase connect grounding wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An approp...

Page 4: ...g conductor cable on the UPS or the building wiring terminals under any circumstance The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks...

Page 5: ...lowing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package should contain One UPS One user manual One monitoring software CD option please check...

Page 6: ...4 2 2 Wiring Terminal View Diagram 1 10K 15K 20K L Diagram 2 10K 15K 20K L Rear Panel DUAL Rear Panel Diagram 3 10K 15K 20K L Diagram 4 10K 15K 20K L Input Output Terminal DUAL Input Output Terminal...

Page 7: ...5 Diagram 5 30K L Rear Panel Diagram 6 40K L Rear Panel Diagram 7 30K L 40K L Dual Input Input Output Terminal...

Page 8: ...6 Diagram 8 60KL front view Diagram 9 80KL front view with door open with door open Diagram 10 60KL 80KL Input Output Terminal...

Page 9: ...e as the input power source for the UPS as its rated current is less than the UPS s maximum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building befo...

Page 10: ...15K L 20K L Terminal block wiring diagram for 10K L 15K L 20K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram HV 60KL 80KL T...

Page 11: ...ion to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The Connection with wrong battery...

Page 12: ...gram of parallel system for 10K L 15K L 20K L a Wiring diagram of parallel system for 10K L 15K L 20K L Wiring diagram of parallel system for 30K L 40K L Wiring diagram of parallel system for 30K L DU...

Page 13: ...iring diagram of parallel system for 60KL 80KL 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation Please download the...

Page 14: ...er into the sub screen MAIN Initializing INFORMATION CONTROL SETTING DATA LOG MEASURE ON OFF UPS BATTERY TEST MUTE ALL MEASURE1 MEASURE2 MEASURE3 BASIC ADVANCE BASIC1 BASIC2 ELECTRICAL BATTERY MISCELL...

Page 15: ...n 0 0 Screen 1 0 Control screen with common control operation Screens 1 1 1 to start and stop the unit through the control panel Enter YES to turn on or turn off UPS And screen will jump to main scree...

Page 16: ...attery test are Battery testing The battery test is running Battery Test failed The battery test has been failed Screen 1 1 3 to order cancel mute of UPS Enter YES to make UPS mute Press BACK or No ic...

Page 17: ...hases to neutral for three phase or single phase units 0 1V Bypass voltages phase to phase units 0 1V Bypass voltages phases to neutral for three phase or single phase units 0 1V Output voltages phase...

Page 18: ...can program the time hh mm ss hours minutes seconds and the date dd mm yy day month year You can select the display language between the available options it may vary You can select input source Line...

Page 19: ...level an authorized password will be required to modify some advanced parameters Screens 3 1 2 Advance settings Screens 3 1 2 1 You can select the output voltage between the following options 208V 220...

Page 20: ...an select the ECO frequency range The range of frequency goes from 46Hz to 54Hz when UPS is 50Hz system and goes from 56 Hz to 64 Hz when UPS is 60Hz system You can select Whether UPS is enable or dis...

Page 21: ...rmation To modify the rated values on the screens it is necessary to introduce the Password on the previous screen 3 0 otherwise they only will be able to be visualized The basic information shows UPS...

Page 22: ...ere are all the possible alarms displayed in the display LCD 3 3 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4...

Page 23: ...f the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 8...

Page 24: ...ns that there are problems for UPS operation Users can get the warning indicator from LCD panel Please check the trouble shooting table in Chapter 4 for details 2 Some warning alarms can t be muted un...

Page 25: ...er the UPSs enter to Battery mode and add to the parallel system d If you have the third UPS follow the same procedure of c Then the parallel system is complete If more detail information is needed pl...

Page 26: ...e short circuited None 64 Voltage waveform abnormal in B phase None 18 Inverter B C output line to line short circuited None 65 Voltage waveform abnormal in C phase None 19 Inverter C A output line to...

Page 27: ...ed position to disable the EPO function The warning code 01 The external or internal battery is incorrectly connected Check if all batteries are connected well The warning code 09 UPS is overload Remo...

Page 28: ...acks which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the te...

Page 29: ...7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah N A Numbers 10 10 pcs 16 16 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 2 0 A 10 Recommended 1 0 12 0A Adjustable Charging Vol...