UPS  will  shut  down  automatically  to  protect  the  battery.  This  battery  discharge  protection  can  be 

enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section).   

6. Test the batteries 

1)    If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could refer 

to 

Screen 1.1-2

2)    Users also can set battery self-test through monitoring software. 

7. Turn off the UPS with utility power supply in AC mode 

1)    Refer to 

Screens 1.1-1

.

 

NOTE 1: 

If the UPS has been set to bypass output, it will bypass voltage from the utility power to output 

terminal even though you have turned off the UPS (inverter). 

NOTE 2:

 After turning off the UPS, please be aware that the UPS is working at Bypass mode and there is 

risk of power loss for connected devices.   

2)    In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the 

line input breaker(for dual input unit, also switch off the bypass line breaker). A few seconds later, there 

is no display shown on the display panel and UPS is complete off. 

8. Turn off the UPS without utility power supply in Battery mode 

1)    Refer to 

Screens 1.1-1

2)    Then UPS will cut off power to output and there is no display shown on the display panel. 

9. Mute the buzzer 

1)    Refer to 

Screen 1.1-3.

 

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for details.   

10. Operation in warning status 

1)    When Fault LED illuminates and the buzzer beeps once every second, it means that there are problems 

for  UPS  operation.  Users  can  get  the  warning  indicator  from  LCD  panel.  Please  check  the  trouble 

shooting table in Chapter 4 for details.   

2)    Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for details. 

11. Operation in Fault mode 

1)    When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the 

UPS.    Users  can  get  the  fault  code  from  display  panel.  Please  check  the  trouble  shooting  table  in 
Chapter 4 for details.

 

2)    Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to 

turn  on  the  UPS  again  before  solving  the  issue.  If  the  problems  can’t  be  fixed,  please  contact  the 

distributor or service personnel immediately. 

3)    For emergency case, please cut off connection from utility, external battery, and output immediately to 

avoid more risk or danger.   

12. Operation in maintaining bypass mode   

This operation is only available for professional or qualified technicians.

     

When the UPS needs to repair or service and then the load can’t be shut off, the UPS needs to turn to 
maintenance mode.   
1) First, turn off the UPS. 
2) Second, remove the cover of maintenance bypass switch on the panel. 
3) Third, turn the maintenance switch to “BPS” position and turn off the UPS input breaker and output 

breaker. 

3-5. Parallel Operation 

1. Parallel system initial startup 

Please make sure that all of the running UPSs are parallel models and have the same configuration. 
1)

 

Turn on each UPS in AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter output 

voltage of each phase for each UPS to if the inverter voltage difference between actual output and 

Summary of Contents for VFI 10KL CPG PF1 3/3

Page 1: ...PowerWalker VFI 10K 80K CPG PF1 3 3 Uninterruptible Power Supply System Version 1 0 1...

Page 2: ...E 26 5 2 MAINTENANCE 26 6 SPECIFICATIONS 27 Please comply with all warnings and operating instructions in this manual This equipment should only be installed serviced and maintained by qualified perso...

Page 3: ...n the final installation phase connect grounding wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An approp...

Page 4: ...g conductor cable on the UPS or the building wiring terminals under any circumstance The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks...

Page 5: ...lowing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package should contain One UPS One user manual One monitoring software CD option please check...

Page 6: ...4 2 2 Wiring Terminal View Diagram 1 10K 15K 20K L Diagram 2 10K 15K 20K L Rear Panel DUAL Rear Panel Diagram 3 10K 15K 20K L Diagram 4 10K 15K 20K L Input Output Terminal DUAL Input Output Terminal...

Page 7: ...5 Diagram 5 30K L Rear Panel Diagram 6 40K L Rear Panel Diagram 7 30K L 40K L Dual Input Input Output Terminal...

Page 8: ...6 Diagram 8 60KL front view Diagram 9 80KL front view with door open with door open Diagram 10 60KL 80KL Input Output Terminal...

Page 9: ...e as the input power source for the UPS as its rated current is less than the UPS s maximum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building befo...

Page 10: ...15K L 20K L Terminal block wiring diagram for 10K L 15K L 20K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram HV 60KL 80KL T...

Page 11: ...ion to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The Connection with wrong battery...

Page 12: ...gram of parallel system for 10K L 15K L 20K L a Wiring diagram of parallel system for 10K L 15K L 20K L Wiring diagram of parallel system for 30K L 40K L Wiring diagram of parallel system for 30K L DU...

Page 13: ...iring diagram of parallel system for 60KL 80KL 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation Please download the...

Page 14: ...er into the sub screen MAIN Initializing INFORMATION CONTROL SETTING DATA LOG MEASURE ON OFF UPS BATTERY TEST MUTE ALL MEASURE1 MEASURE2 MEASURE3 BASIC ADVANCE BASIC1 BASIC2 ELECTRICAL BATTERY MISCELL...

Page 15: ...n 0 0 Screen 1 0 Control screen with common control operation Screens 1 1 1 to start and stop the unit through the control panel Enter YES to turn on or turn off UPS And screen will jump to main scree...

Page 16: ...attery test are Battery testing The battery test is running Battery Test failed The battery test has been failed Screen 1 1 3 to order cancel mute of UPS Enter YES to make UPS mute Press BACK or No ic...

Page 17: ...hases to neutral for three phase or single phase units 0 1V Bypass voltages phase to phase units 0 1V Bypass voltages phases to neutral for three phase or single phase units 0 1V Output voltages phase...

Page 18: ...can program the time hh mm ss hours minutes seconds and the date dd mm yy day month year You can select the display language between the available options it may vary You can select input source Line...

Page 19: ...level an authorized password will be required to modify some advanced parameters Screens 3 1 2 Advance settings Screens 3 1 2 1 You can select the output voltage between the following options 208V 220...

Page 20: ...an select the ECO frequency range The range of frequency goes from 46Hz to 54Hz when UPS is 50Hz system and goes from 56 Hz to 64 Hz when UPS is 60Hz system You can select Whether UPS is enable or dis...

Page 21: ...rmation To modify the rated values on the screens it is necessary to introduce the Password on the previous screen 3 0 otherwise they only will be able to be visualized The basic information shows UPS...

Page 22: ...ere are all the possible alarms displayed in the display LCD 3 3 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4...

Page 23: ...f the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 8...

Page 24: ...ns that there are problems for UPS operation Users can get the warning indicator from LCD panel Please check the trouble shooting table in Chapter 4 for details 2 Some warning alarms can t be muted un...

Page 25: ...er the UPSs enter to Battery mode and add to the parallel system d If you have the third UPS follow the same procedure of c Then the parallel system is complete If more detail information is needed pl...

Page 26: ...e short circuited None 64 Voltage waveform abnormal in B phase None 18 Inverter B C output line to line short circuited None 65 Voltage waveform abnormal in C phase None 19 Inverter C A output line to...

Page 27: ...ed position to disable the EPO function The warning code 01 The external or internal battery is incorrectly connected Check if all batteries are connected well The warning code 09 UPS is overload Remo...

Page 28: ...acks which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the te...

Page 29: ...7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah N A Numbers 10 10 pcs 16 16 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 2 0 A 10 Recommended 1 0 12 0A Adjustable Charging Vol...

Reviews: