background image

23 

 

setting value is less than 1.5V(typical 1V) with multimeter. If the difference is more than 1.5V, please 

calibrate the voltage by configuring inverter voltage adjustment(Refer to Program 15,16 and 17,section 
3-7) in LCD setting. If the voltage remains more than 1.5V after calibration, please contact your local 

distributor or service center for help. 

2)

 

Calibrate the output voltage measurement by configuring output voltage calibration(Refer to Program 

18,19, and 20, section 3-7) in LCD setting to make sure the difference between real output voltage and 
detected value of UPS is less than 1V. 

3)  Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.   
4)  Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one with the 

parallel cable and share current cable, and then screw the cover back. 

5) 

  Turn on the parallel system in AC mode:

 

a)

 

Turn on the line input breaker of each UPS (for dual input, also turn on bypass input breaker). After 

all UPSs enter to bypass mode, measure the output voltage between two UPSs for the same phase 
to make sure the phase sequence is correct. If these two voltage differences are near to zero, that 

means all connections are met. Otherwise, please check if the wirings are connected correctly. 

b)

 

Turn on the output breaker of each UPS. 

c)

 

Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and then, 

the parallel system is now complete. 

6)   

Turn on the parallel system in Battery mode:

 

a)

 

Turn on the battery breaker (only available in long-run model) and

 

output breaker of each UPS. 

b)

 

Turn on any UPS. A few seconds later, the UPS will enter to battery mode. 

c)

 

Turn on another UPS. A few seconds later, the UPSs enter to Battery mode and add to the parallel 

system.   

d)

 

If you have the third UPS, follow the same procedure of c). Then, the parallel system is complete. 

If more detail information is needed, please contact supplier or service center for parallel operation 

instruction. 
2. Add new units into the parallel system 

1)    You can’t add one new unit into the parallel system when whole system is running. You must cut off the 

load and shutdown the system.   

2)    Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-4. 
3)    Install the new parallel system refers to the previous section. 
 

3. Remove units from the parallel system 

There are two methods to remove units from the parallel system: 
First method: 

1)

 

Press the “OFF”  iron twice. Then, the UPS will enter into Bypass mode or No Output mode without 

output.   

2)

 

Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 

3)

 

After it shuts down, you can turn off the battery breaker (for long-run model) and remove the parallel 

and share current cables. And then remove the unit from the parallel system. 

 

Second method: 

1)

 

If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load 

and shut down the system first. 

2)

 

Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs will 

transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance switches 

from “UPS” to “BPS” position. Turn off all the input breakers and battery breakers in parallel system.   

3)

 

Turn off the output breaker and remove the parallel cable and share current cable of the UPS which you 

want to remove. Now, you can remove the UPS from parallel system. 

4)

 

Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode.

 

Set the 

maintenance switches from “BPS” to “UPS position and put the maintenance bypass covers back on.   

Summary of Contents for VFI 10KL CPG PF1 3/3

Page 1: ...PowerWalker VFI 10K 80K CPG PF1 3 3 Uninterruptible Power Supply System Version 1 0 1...

Page 2: ...E 26 5 2 MAINTENANCE 26 6 SPECIFICATIONS 27 Please comply with all warnings and operating instructions in this manual This equipment should only be installed serviced and maintained by qualified perso...

Page 3: ...n the final installation phase connect grounding wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An approp...

Page 4: ...g conductor cable on the UPS or the building wiring terminals under any circumstance The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks...

Page 5: ...lowing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package should contain One UPS One user manual One monitoring software CD option please check...

Page 6: ...4 2 2 Wiring Terminal View Diagram 1 10K 15K 20K L Diagram 2 10K 15K 20K L Rear Panel DUAL Rear Panel Diagram 3 10K 15K 20K L Diagram 4 10K 15K 20K L Input Output Terminal DUAL Input Output Terminal...

Page 7: ...5 Diagram 5 30K L Rear Panel Diagram 6 40K L Rear Panel Diagram 7 30K L 40K L Dual Input Input Output Terminal...

Page 8: ...6 Diagram 8 60KL front view Diagram 9 80KL front view with door open with door open Diagram 10 60KL 80KL Input Output Terminal...

Page 9: ...e as the input power source for the UPS as its rated current is less than the UPS s maximum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building befo...

Page 10: ...15K L 20K L Terminal block wiring diagram for 10K L 15K L 20K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram HV 60KL 80KL T...

Page 11: ...ion to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The Connection with wrong battery...

Page 12: ...gram of parallel system for 10K L 15K L 20K L a Wiring diagram of parallel system for 10K L 15K L 20K L Wiring diagram of parallel system for 30K L 40K L Wiring diagram of parallel system for 30K L DU...

Page 13: ...iring diagram of parallel system for 60KL 80KL 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation Please download the...

Page 14: ...er into the sub screen MAIN Initializing INFORMATION CONTROL SETTING DATA LOG MEASURE ON OFF UPS BATTERY TEST MUTE ALL MEASURE1 MEASURE2 MEASURE3 BASIC ADVANCE BASIC1 BASIC2 ELECTRICAL BATTERY MISCELL...

Page 15: ...n 0 0 Screen 1 0 Control screen with common control operation Screens 1 1 1 to start and stop the unit through the control panel Enter YES to turn on or turn off UPS And screen will jump to main scree...

Page 16: ...attery test are Battery testing The battery test is running Battery Test failed The battery test has been failed Screen 1 1 3 to order cancel mute of UPS Enter YES to make UPS mute Press BACK or No ic...

Page 17: ...hases to neutral for three phase or single phase units 0 1V Bypass voltages phase to phase units 0 1V Bypass voltages phases to neutral for three phase or single phase units 0 1V Output voltages phase...

Page 18: ...can program the time hh mm ss hours minutes seconds and the date dd mm yy day month year You can select the display language between the available options it may vary You can select input source Line...

Page 19: ...level an authorized password will be required to modify some advanced parameters Screens 3 1 2 Advance settings Screens 3 1 2 1 You can select the output voltage between the following options 208V 220...

Page 20: ...an select the ECO frequency range The range of frequency goes from 46Hz to 54Hz when UPS is 50Hz system and goes from 56 Hz to 64 Hz when UPS is 60Hz system You can select Whether UPS is enable or dis...

Page 21: ...rmation To modify the rated values on the screens it is necessary to introduce the Password on the previous screen 3 0 otherwise they only will be able to be visualized The basic information shows UPS...

Page 22: ...ere are all the possible alarms displayed in the display LCD 3 3 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4...

Page 23: ...f the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 8...

Page 24: ...ns that there are problems for UPS operation Users can get the warning indicator from LCD panel Please check the trouble shooting table in Chapter 4 for details 2 Some warning alarms can t be muted un...

Page 25: ...er the UPSs enter to Battery mode and add to the parallel system d If you have the third UPS follow the same procedure of c Then the parallel system is complete If more detail information is needed pl...

Page 26: ...e short circuited None 64 Voltage waveform abnormal in B phase None 18 Inverter B C output line to line short circuited None 65 Voltage waveform abnormal in C phase None 19 Inverter C A output line to...

Page 27: ...ed position to disable the EPO function The warning code 01 The external or internal battery is incorrectly connected Check if all batteries are connected well The warning code 09 UPS is overload Remo...

Page 28: ...acks which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the te...

Page 29: ...7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah N A Numbers 10 10 pcs 16 16 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 2 0 A 10 Recommended 1 0 12 0A Adjustable Charging Vol...

Reviews: