Symptom 

Possible cause 

Remedy 

The warning code 0A. 

Fan is locked or not working. Or 

the UPS temperature is too high.  Check fans and notify dealer.   

The warning code 02. 

The  input  neutral  wire  is 

disconnected. 

Check  and  correct  the  input 
neutral  connection.  If  the 

connection is ok and the warning 

is still displaying, please refer to 
the LCD setting section, to enter 

the neutral loss check menu, to 

see if the parameter3 is “CHE”. 

If it is, please press the “Enter” 
key  firstly  to  make  the  “CHE” 

flash  and  press  the  “Enter” key 

secondly to make the UPS clear 
the  alarm.  If  the  warning  still 

exists, please check input fuses 

of L2 and L3. 

The  L2  or  L3  input  fuse  is 

broken. 

Replace the fuse. 

 

5. Storage and Maintenance 

5-1. Storage   

Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. 
During storage, recharge the battery in accordance with the following table: 

Storage Temperature 

Recharge Frequency 

Charging Duration 

-25°C - 40°C 

Every 3 months 

1-2 hours 

40°C - 45°C 

Every 2 months 

1-2 hours 

5-2. Maintenance   

 

  The  UPS  system  operates  with  hazardous  voltages.  Repairs  may  be  carried  out  only  by  qualified 

maintenance personnel.   

 

  Even after the unit is disconnected from the mains, components inside the UPS system are still connected to 

the battery packs which are potentially dangerous.   

 

  Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no 
current  is  present  and  no  hazardous  voltage  exists  in  the  terminals  of  high  capability  capacitor  such  as 

BUS-capacitors.   

 

  Only  persons  are  adequately  familiar  with  batteries and  with  the  required  precautionary  measures  may 

replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.   

 

  Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. 
In  this  product,  the  battery  circuit  is  not isolated  from  the  input  voltage.  Hazardous  voltages  may  occur 

between the battery terminals and the grounding/earthing.   

 

  Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches, 

rings and other metal person objects before maintenance or repair, and only use tools with insulated grips and 
handles for maintaining or repairing. 

 

  When replace the batteries, install the same number and same type of batteries.   

 

  Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries 
must be deposed according to local environmental regulations. 

 

  Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.   

 

  Please replace the fuse only with the same type and amperage in order to avoid fire hazards.   

 

  Do not disassemble the UPS system. 

 

Summary of Contents for VFI 10KL CPG PF1 3/3

Page 1: ...PowerWalker VFI 10K 80K CPG PF1 3 3 Uninterruptible Power Supply System Version 1 0 1...

Page 2: ...E 26 5 2 MAINTENANCE 26 6 SPECIFICATIONS 27 Please comply with all warnings and operating instructions in this manual This equipment should only be installed serviced and maintained by qualified perso...

Page 3: ...n the final installation phase connect grounding wire to the external UPS battery cabinets or appropriate grounding terminals The UPS can be installed only by qualified maintenance personnel An approp...

Page 4: ...g conductor cable on the UPS or the building wiring terminals under any circumstance The UPS system features its own internal current source batteries The UPS output sockets or output terminal blocks...

Page 5: ...lowing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package should contain One UPS One user manual One monitoring software CD option please check...

Page 6: ...4 2 2 Wiring Terminal View Diagram 1 10K 15K 20K L Diagram 2 10K 15K 20K L Rear Panel DUAL Rear Panel Diagram 3 10K 15K 20K L Diagram 4 10K 15K 20K L Input Output Terminal DUAL Input Output Terminal...

Page 7: ...5 Diagram 5 30K L Rear Panel Diagram 6 40K L Rear Panel Diagram 7 30K L 40K L Dual Input Input Output Terminal...

Page 8: ...6 Diagram 8 60KL front view Diagram 9 80KL front view with door open with door open Diagram 10 60KL 80KL Input Output Terminal...

Page 9: ...e as the input power source for the UPS as its rated current is less than the UPS s maximum input current The receptacle may be damaged and destroyed 2 Switch off the mains switch in the building befo...

Page 10: ...15K L 20K L Terminal block wiring diagram for 10K L 15K L 20K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram for 30K L 40K L Terminal block wiring diagram HV 60KL 80KL T...

Page 11: ...ion to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultaneously The Connection with wrong battery...

Page 12: ...gram of parallel system for 10K L 15K L 20K L a Wiring diagram of parallel system for 10K L 15K L 20K L Wiring diagram of parallel system for 30K L 40K L Wiring diagram of parallel system for 30K L DU...

Page 13: ...iring diagram of parallel system for 60KL 80KL 2 5 Software Installation For optimal computer system protection install UPS monitoring software to configure UPS shutdown operation Please download the...

Page 14: ...er into the sub screen MAIN Initializing INFORMATION CONTROL SETTING DATA LOG MEASURE ON OFF UPS BATTERY TEST MUTE ALL MEASURE1 MEASURE2 MEASURE3 BASIC ADVANCE BASIC1 BASIC2 ELECTRICAL BATTERY MISCELL...

Page 15: ...n 0 0 Screen 1 0 Control screen with common control operation Screens 1 1 1 to start and stop the unit through the control panel Enter YES to turn on or turn off UPS And screen will jump to main scree...

Page 16: ...attery test are Battery testing The battery test is running Battery Test failed The battery test has been failed Screen 1 1 3 to order cancel mute of UPS Enter YES to make UPS mute Press BACK or No ic...

Page 17: ...hases to neutral for three phase or single phase units 0 1V Bypass voltages phase to phase units 0 1V Bypass voltages phases to neutral for three phase or single phase units 0 1V Output voltages phase...

Page 18: ...can program the time hh mm ss hours minutes seconds and the date dd mm yy day month year You can select the display language between the available options it may vary You can select input source Line...

Page 19: ...level an authorized password will be required to modify some advanced parameters Screens 3 1 2 Advance settings Screens 3 1 2 1 You can select the output voltage between the following options 208V 220...

Page 20: ...an select the ECO frequency range The range of frequency goes from 46Hz to 54Hz when UPS is 50Hz system and goes from 56 Hz to 64 Hz when UPS is 60Hz system You can select Whether UPS is enable or dis...

Page 21: ...rmation To modify the rated values on the screens it is necessary to introduce the Password on the previous screen 3 0 otherwise they only will be able to be visualized The basic information shows UPS...

Page 22: ...ere are all the possible alarms displayed in the display LCD 3 3 Audible Alarm Description Buzzer status Muted UPS status Bypass mode Beeping once every 2 minutes Yes Battery mode Beeping once every 4...

Page 23: ...f the UPS is overload the buzzer will beep twice every second 4 When the UPS is overload please remove some loads immediately It is recommended to have the total loads connected to the UPS less than 8...

Page 24: ...ns that there are problems for UPS operation Users can get the warning indicator from LCD panel Please check the trouble shooting table in Chapter 4 for details 2 Some warning alarms can t be muted un...

Page 25: ...er the UPSs enter to Battery mode and add to the parallel system d If you have the third UPS follow the same procedure of c Then the parallel system is complete If more detail information is needed pl...

Page 26: ...e short circuited None 64 Voltage waveform abnormal in B phase None 18 Inverter B C output line to line short circuited None 65 Voltage waveform abnormal in C phase None 19 Inverter C A output line to...

Page 27: ...ed position to disable the EPO function The warning code 01 The external or internal battery is incorrectly connected Check if all batteries are connected well The warning code 09 UPS is overload Remo...

Page 28: ...acks which are potentially dangerous Before carrying out any kind of service and or maintenance disconnect the batteries and verify that no current is present and no hazardous voltage exists in the te...

Page 29: ...7 Ah 12 V 9 Ah 12 V 7 Ah 12 V 9 Ah N A Numbers 10 10 pcs 16 16 pcs x 2 strings Recharge Time 9 hours recover to 90 capacity Charging Current max 2 0 A 10 Recommended 1 0 12 0A Adjustable Charging Vol...

Reviews: