Installation and operator’s manual
Page 41 of 65
PVI-2000-OUTD-AU Rev.: 1.0)
Alarm n.
Message
Warning
code
Error
code
Description
1
Sun Low
W001
//
Input voltage under threshold ( when
OFF )
2
Input OC
//
E001
Input Over current
3
Input UV
W002
//
Input Undervoltage
4 Input
OV
// E002
Input
Overvoltage
6 Int.Error
// E003
No
parametres
7 Bulk
OV
// E004
Bulk
Overvoltage
8 Int.Error
// E005
Communication
error
9
Out OC
//
E006
Output Overcurrent
10 Int.
Error
// E007
IGBT
Sat
11 Int.Error
// E008
Bulk
Undervoltage
12 Int.Error
// E009
Internal
error
13
Grid Fail
W003
//
Incorrect grid parametres
14 Int.Error
// E010
Bulk
Low
15 Int.Error
// E011
Ramp
Fail
16
DC/DC Fail
//
E012
DcDc error detected by the inverter
17
Not used in
PVI-2000
// E013
No
parameters
18 ----------
//
//
--------------
19
Over Temp.
//
E014
Internal overtemperature
20
Cap. Fault
//
E015
Bulk capacitor fail
21
Inv. Fail
//
E016
Inverter fail detected by the DcDc
22 Int.Error
// E017
Start
Timeout
23 Ground
F.
// E018
Ileak
fail
24 ----------
//
//
---------------
25
Int.Error
//
E019
Ileak sensor fail
26
DC/DC Fail
//
E012
DcDc error detected by the inverter
27
Int.Error
//
E020
inverter relay fail
28
Int.Error
//
E021
DcDc relay fail
29
Int.Error
//
E019
Ileak sensor fail
30 Int.Error
// E022
Autotest
Timeout
31 Int.Error
// E023
Dc-Injection
Error
32 Grid
OV
W004 // Output
Overvoltage
33 Grid
UV
W005 // Output
Undervoltage
34 Grid
OF
W006 // Output
Overfrequency
35 Grid
UF
W007 // Output
Underfrequency
36
Z Grid HI
W008
//
Z grid out of range
37 Int.Error
// E024
Internal
error
38
-----------
//
E025
Low insulation resistance ( log only )
39
Int.Error
//
E026
Wrong reference voltage (VRef)
40 Int.Error
// E027
Wrong grid voltage measurement (
VGrid )
41 Int.Error
// E028
Wrong grid frequency measurement
( FGrid )
42 Int.Error
// E029
Wrong grid impedance