Install the expansion screws in the wall so that the head of the screws is about
4mm (
~
1/6”) from the wall surface. Then hang AURORA on the wall by fitting
the screw heads in the mounting slots as shown in Fig.7, and secure the screws.
Fig.7 AURORA wall mounting
It is possible to mount AURORA in a tilted position. In that case the thermal
dissipation will not be optimized and the unit may derate the maximum output
power at ambient temperatures below 40°C (see Fig. 9).
NOTE:
In case of installation of several units, Power-One
recommends not to install them in parallel, superimposed, rows.
In fact the heat generated by the bottom rows will get the ambient
temperature of the upper inverters to increase. At ambient temperatures higher than +
40 °C an output power derating may occur on the top units.