User Manual
Page 56 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
Fig. 22: Alarm contacts terminal block
This function can activate two alarm modes. Press ENTER to open the relevant
submenu:
An arrow on the left side of the display highlights your current selection. When an
item is selected, press ENTER to confirm activation of chosen mode.
PRODUCTION
: Relay is only activated when the inverter is connected to the grid
(contact closing across terminals “N.O.” and “C”)
FAULT
: triggers relay activation (contact closing across terminals “N.O.” and
“C”), only when an error signal occurs, i.e. when grid is disconnected, excluding
Input Undervoltage.
5.5.6.11
Remote control
This function is used to disable the inverter’s manual shutdown. Operation is as
follows:
- set to ENABLE to activate manual ON/OFF function
- set to DISABLE to disable manual ON/OFF function, so that the inverter will be
automatically controlled only by the input voltage.
Manual ON and OFF input is read on inverter digital input. When set to OFF, the
display will cycle through the following screens:
Production
Fault
Remote ON/OFF
Disable
Remote ON/OFF
Enable
Summary of Contents for AURORA PVI-6000-OUT-US-W
Page 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Page 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Page 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...