User Manual
Page 26 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
WARNING:
Do not reverse line and neutral as it might make the
system unsafe to run and cause malfunctioning.
NOTE
: If you have installed a meter between the AC disconnect and the
AURORA inverter, follow the procedure outlined above when
connecting to the meter.
Step 5/6: Connect AURORA to the Rectifier/Wind Interface Box
WARNING:
Prior to connecting the AURORA inverter to the rectifier
check, using a proper meter, that the polarity and the voltage value
between the positive and negative terminal are correct. The output voltage
polarity from the rectifier should match the “+” and “-” symbols.
Referring to Fig.12 use the following procedure:
1)
Verify the presence of the two wires connecting the two DC input
channels in parallel (the inverter is shipped from the factory with the
two wires already connected).
2)
Connect the positive DC cable from the rectifier or Wind Interface to
the positive terminal block inside the AURORA inverter (red cable
on Fig 12).
3)
Connect the negative DC cable from the rectifier or Wind Interface
to the negative terminal block inside the AURORA inverter (black
cable on Fig 12).
Summary of Contents for AURORA PVI-6000-OUT-US-W
Page 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Page 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Page 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...