User Manual
Page 13 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
WARNING
: The DC voltage input to the inverter shall not exceed
600Vdc for any reason, in order to avoid damage to the equipment.
NOTE:
A minimum input voltage of 50Vdc is required for the AURORA inverter
to start the grid connection sequence. Once connected, the AURORA
inverter will transfer the maximum power available for any input DC
voltage value in a 50V to 580Vdc range to the grid.
The max output current from the generator or an interface device shall be always
within the inverter limits. In the AURORA inverter the total max input current is
36Adc.
Fig. 3 Wind energy system diagram
Wind
Turbine
Generator
Rectifier/
Interface
DC Voltage
AC Voltage
AC Grid
AC disconnect
(3-pole)
DC Disconnect
(2-pole)