User Manual
Page 23 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
Fig.9. Wiring diagram
WARNING
: When disconnecting the AURORA inverter, always open
the AC disconnect switches to disconnect the inverter from the grid and
from the generator. Wait until the LEDs on the front panel turn off before
unplugging the multiple contact connections from the DC input.
WARNING:
When selecting the power supply cables for AURORA
connections, carefully consider nominal operating voltage, insulation
voltage, maximum operating temperature, current density and
flammability rating. All of these values must comply with the maximum
current density ratings required by applicable local rules. A key
parameter to consider in cable selection is cable loss, as exceeding loss
will lead to lower efficiency.
The maximum diameter allowed for the conductors to be assembled to the
terminal blocks for grid connection is 0.16”. The supplied M32 cable
gland accepts wires up to 0.19”.
The following items are located on the bottom of the inverter (see Fig. 10, from
right to left):
¾
Two holes sealed with waterproof caps. Remove the caps to gain access to the
connectors for data serial transfer via the RS485 port. One hole is for the
input serial cable and the other for an output cable, if fitted (output cable is
required when several inverters are connected in a daisy-chain configuration,
see Section 6).
AC
Disconnect
switch
3-phase
Max. Rating
40A/400Vac
Loads
Rete
AC
Disconnect
switch
Max. Rating
40A/240Vac
Rectifier/
Wind
Interface
Generator
Summary of Contents for AURORA PVI-6000-OUT-US-W
Page 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Page 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Page 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...