User Manual
Page 22 of 77
(PVI-6000-OUTD-US-W Rev.2.0)
3.5
Before performing electrical connections
WARNING:
Electrical connections shall be performed only after the
AURORA inverter is securely mounted to the wall.
WARNING
: The connection of the AURORA inverter to the electrical
distribution grid must be performed by qualified operators and only after
receiving authorization from the utility that operates the grid.
WARNING:
For a step-by-step description of the correct procedure,
please, read and follow the instructions provided in this section (and its
subsections) while observing all safety warnings. Any operation that
does not comply with the instructions can lead to conditions hazardous
to personnel and/or equipment damage.
WARNING:
Always respect the nominal ratings of voltage and current
defined in Section 8 (Technical Characteristics) when designing your
system. When designing the system make sure the following limits are
never exceeded:
¾
Maximum DC voltage input: 600Vdc under any condition.
¾
Maximum DC current input to the 2 parallel input: 32Adc under
any condition.
WARNING:
Check the National and local standards and regulations to
make sure your electrical installation and design are in compliance with
them.
NOTE
: In accordance with the typical assembly diagram (see Fig. 9) an
AC disconnect switch with the overload protection (breaker) must be
used to connect the AURORA inverter to the grid. Recommended ratings
for the disconnect switch are 40A, 240VAC.
Summary of Contents for AURORA PVI-6000-OUT-US-W
Page 1: ...AURORA Wind Inverters INSTALLATION AND OPERATION MANUAL Model number PVI 6000 OUT US W Rev 2 0...
Page 32: ...User Manual Page 32 of 77 PVI 6000 OUTD US W Rev 2 0 Fig 17 Data Transmission Options...
Page 60: ...User Manual Page 60 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 73: ...User Manual Page 73 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 74: ...User Manual Page 74 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 75: ...User Manual Page 75 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 76: ...User Manual Page 76 of 77 PVI 6000 OUTD US W Rev 2 0...
Page 77: ...User Manual Page 77 of 77 PVI 6000 OUTD US W Rev 2 0...