5-50
PFC-6075 • 5403593 • Rev C • 2/13
LEARN Programming
The LeARN mode enables you to efficiently configure all connected, addressed
input and output devices. (
Refer to
Section 3: Installation – Addressing SLC Devices, for detailed instructions
.) Only authorized users may access this function.
LeARN generates a list of all points, which may be viewed through the Points and Zones functions on a remote computer
.
(Refer to the “Configuring Points” and “Mapping Zones” sections for details.)
To run the LEARN mode:
From the control panel, press the
1.
Enter button
to display the
Main Menu.
Press
•
6
to select
Programming.
The
"Enter Code" prompt
displays.
enter the user code as prompted. The “
•
1 Learn” prompt
displays.
Press
•
1
to select
LEARN
. The
"SLC Initializing" prompt
displays, and the system begins the initialization process.
Results are grouped by
2.
device type
. If no changes are detected, the prompt
“No changes”
displays.
Use do
•
wn arrow
to scroll through results by device type:
1
=P-Link Found
2
=P-Link Removed
3
=Pts Found
4
=Pts Removed
5
=Pts Changed
Esc
=exit
Note:
The abbreviation
“Pts” refers to addressable SLC points.
Select
•
Esc
when finished reviewing results. The system prompts to save or discard file.
Press
3.
1
to
save
changes; press
2
to
discard
changes.
If option
•
1
is selected, the
“Accept confirmation” prompt
displays.
Press
•
Enter
to accept or
Esc
to discard.
Press
4.
Esc
to exit programming menu.
Connecting the Computer and Panel
This section provides instructions on setting up connectivity between a laptop or networked computer and the control panel. Once
this is achieved, you may program your system using the panel configuration software.
Note
: These instructions are relevant to all system configurations. If your PC connects directly to the panel, any
procedural differences are noted throughout.
Connecting a Computer to the Panel via a Network:
Connect cable to the ethernet port on network (or directly to the panel if not using a network)
1.
.
2.
Connect ethernet cable to port as shown below.
Control Panel Ethernet Port