5-54
PFC-6075 • 5403593 • Rev C • 2/13
Enter
4.
IP address
or
panel name
in the
“Transfer Via IP” field.
Notes:
To capture your panel’s unique IP address, disconnect the ethernet cable from panel. The message
•
“Ethernet Lost”
displays indicating connectivity is lost. Be prepared to write down the address, and reconnect cable.
If you are connecting via a modem, please refer to
•
“
Appendix B: Modem Connectivity Setup
”.
Click
5.
OK.
The
Transfers region
displays the uploaded file.
Example of Transfers Download Results
Figure 67.
Double-click on the transfer file to display results.
•
All points detected during the LeARN process have been uploaded to the panel configuration software.
•
Note
: Details on viewing and configuring points are addressed in detail later in the
“System Programming –
Configuring Points”
topic.
Downloading Configuration File to Panel
The
Download Configuration File to Panel icon
allows you to copy all programming changes to the panel.
Notes:
Be sure to "
•
Enable Remote Access"
at the panel before choosing this option. If your PC is directly connected to the
panel versus a network, this step is not necessary.
verify that the
•
Remote User Name and Password
match the panel’s user name and password. You will receive an
error message when attempting to download data to the panel if they do not match.
Enable Remote Access
To enable remote access:
At control panel, press
1.
ENTER
to display the
Main Menu
.
Press
2.
7
to select
Data Transfer
.
The
3.
“ENTER CODE”
prompt displays. enter the user code to continue.
The
4.
Select Data option
displays. Press
1
to select
Remote Access.
Press
5.
ESC
to return to
Main Menu.
Note:
Once enabled, the remote access will “time out” after thirty (30) minutes if contact is not established.