3-32
PFC-6075 • 5403593 • Rev C • 2/13
Remote Annunciators Installation (RA-6500 and RA-6075)
This panel supports up to 31 annunciators in any combination (RA-6500 / RA-6075). The RA-6500 provides a 4 x 40 character
LCD display. Whereas, the RA-6075 provides a 2 x 16 character LCD display, along with standard function and numeric keys. All
annunciator models listed are designed to be mounted on a flat non-condensing surface or electrical box.
Setting Addresses
An annunciator's address is set by dip switch S1, which is located on the back of the annunciator. The address must be set in
the range of one to thirty-one (1–31) to be recognized by the panel.
(Refer to chart on the previous page for P-Link DIP switch
programming.)
Annunciator Back Panel View
Figure 32.
LED Annunciators Installation (LED-16)
The panel supports up to ten (10) LeD-16 annunciators, which display alarm, supervisory, and trouble conditions for up to
16 zones per LeD-16. It also provides Silence and Reset functionality. Blank zone labels are provided for use with the LeD
annunciator to label each zone name or identifier. The labels may be typed or written on the supplied card-stock, and then inserted
into the back of the front panel as shown in the right-most figure below.
Note
: This panel supports up to ten (10) LeD-16 annunciators and/or DRv-50 drivers in any combination.
LED-16 Module & Board
Figure 33.
DWG #608-4
DWG #608-5
Zone labels
will display here
Labels are inserted
here as needed
DIP SWITCH
A
B
+
-
DWG #593-31
S1
P-Link
Connections