Programming Options
Table 9:
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Zone
Zone Type
Y
Alarm
Supervisory
Positive Alarm Sequence
Auxiliary
Fire Drill
System Alarm
System Supervisory
System Trouble
All settings allowed
Zone
Alarm Count
Y
1-10
All settings allowed
Zone
Silenceable
Y
Yes/No
All settings allowed
Zone
Silence Inhibit
Y
Yes/No
All settings allowed
Zone
Auto Silence
Y
Yes/No
All settings allowed
Zone
Auto Unsilence
Y
Yes/No
All settings allowed
Zone
Restore Delay
Y
0-300 Sec
Full range allowed
Zone
Latching
Y
Yes/No
All settings allowed
Zone
Local
Y
Yes/No
All settings allowed
Zone
Output Pattern
Y
Constant
ANSI Temporal
March Code
Double Time
All settings allowed
Zone
Day Sensitivity
Y
1.1%-3.5%
Full range allowed
Within listed range
of sensor
Zone
Night Sensitivity
Y
1.1%-3.5%
Full range allowed
Within listed range
of sensor
Zone
Fixed Heat
Setting
Y
135
̊
F-185
̊
F
Full range allowed
Within listed range
of sensor
Zone
Combo ROR/
Fixed Setting
Y
135
̊
F-174
̊
F
All settings allowed
Within listed range
of sensor
SLC Point
Function
Y
Photo Detector (PSA)
Photo Duct Detector (DSA)
Photo/Heat Detector (PSHA)
Fixed Heat Detector (FHA)
Combination Fixed / ROR Heat
Detector (RHA)
Conv. Zone Module (CIZM)
Mini Contact Mod (MCM)
Single Contact Mod (SCM)
Dual Contact Mod (DCM)
Mon. Output Mod (MOM)
Twin Relay Module (TRM)
Sounder Base (ASB)
Relay Base (ARB)
All settings allowed
Specifies use/type of
SLC device
SLC Point
Dry Contact Input
Functions
Y
Pull Station, Water Flow,
Supervisory, Tamper, Fire Drill,
Trouble Monitor, Aux, Abort,
Reset, Silence, Fire Alarm,
Disable Inputs, Disable Outputs,
Disable Inputs/Outputs, Lamp
Test
All settings allowed
Applies to all dry-
contact input devices
and circuits.