3-23
PFC-6075 • 5403593 • Rev C • 2/13
For a Single Device:
From the
1.
SLC Addr Prog menu
, press
1
to address a
Single device.
Attach connector wires to
2.
SLC PGM
terminals, if not already done. The
“Connect Device” prompt
displays.
Connect device.
3.
The
“Found Address: xx” prompt
displays
.
Modify new address, if needed, or press
y
y
ENTER
to continue.
The
y
y
“
Writing Addr: XX”
prompt
displays, and the system beeps three (3) times when completed.
When addressing is completed, the
“Found Addr: XX, New Addr: XX”
prompt
displays.
Disconnect device, and continue with next device.
y
y
Repeat steps, as needed.
y
y
Press
4.
ESC
when finished.
For Multiple Devices
:
From the
1.
SLC Addr Prog menu
, press
2
to
address
Mult device
.
The “
•y
Start Address: XX” prompt
displays.
Modify starting address, if needed, and press
•y
ENTER
.
The prompt
•y
“Connect Device”
displays.
Connect 1
2.
st
device. The
“Addr = XX Next = XX Remove” prompt
displays.
Disconnect the device, connect next device. Addressing is completed when the panel emits a series of
•y
three (3) beeps
.
The
•y
“Addr = XX Next = XX Remove” prompt
displays.
Continue with next device, following prompts.
•y
Notes:
The prompt
•y
“
Addr = XX”
refers to the current device number, and
“Next = XX”
is the next sequential address number.
When configuring a
•y
Class B DCM-4
, press the
UP ARROW
to skip the next sequential number. The Class B DCM-4
requires 2 addresses; if this isn't done, the next available address will be assigned to a different device and the DCM-4
will operate as a single point device.
Press
3.
ESC
when finished.