5-81
PFC-6075 • 5403593 • Rev C • 2/13
NAC Functions
The four (4) on-board circuits (NACs 1&2, I/O Ckts 1&2) are automatically configured as
“General Purpose”
, but may be
reconfigured and renamed. The I/O circuits have additional configuration options since they may be configured as inputs. Refer to
the two (2) tables below for descriptions of the configuration functions.
NAC & I/O Circuit Configuration Functions
Table 18:
Function
Description
Unused
Circuit is unused.
General Purpose
General purpose NAC; obeys zone “
output pattern
” programming.
Potter Sync
Drives Potter synchronized horns / strobes.
Gentex Sync
Drives Gentex synchronized horns / strobes.
System Sensor Sync
Drives System Sensor synchronized horns / strobes.
Wheelock Sync
Drives Wheelock synchronized horns / strobes.
Aux Constant
Constant DC power.
Aux Resettable
Constant DC power; disconnects power during system reset.
Aux Door Holder
Constant DC power; disconnects when an alarm occurs.
Aux Door Holder Low AC Drop
Constant DC power; disconnects on AC Loss or when an alarm occurs.
Aux ANSI
Always on ANSI pattern used for ASB pattern synchronization.
City Tie
Municipal box connection
I/O Circuit Functions
Table 19:
Function
Description
Input Pull Station
Pull Station Input
Input Water Flow
Water Flow Input obeys water flow delay as defined in “
General Options
”.
Input Supervisory
Supervisory Input
Input Tamper
Tamper Input reports as supervisory.
Input Fire Drill
Fire Drill Input activates a fire drill.
Input Trouble Monitor
Trouble Input creates a trouble condition.
Input Aux
Aux Input reports as untyped alarm.
Input Abort
Abort Input is used only with releasing applications.
Input Release Follower
Release Follow Input causes immediate activation of release solenoid.
Input Reset
Reset input initiates system reset.
Input Silence
Silence Input initiates system silence.
Trigger IO Reverse Polarity
Reverse Polarity Output report trouble.
Trigger IO Reverse Polarity No Trouble
Reverse Polarity Output report no trouble.