9.4 Adjusting relay outputs
The 2 relays can be configured in 2 different modes :
- Mode 1 is used to configure relay R1 on a Redox measurement value and relay R2 on a temperature
measurement value.
- Mode 2 is used to configure relays R1 and R2 on two Redox measurement values.
The 2 relays can be configured with the following attributes :
-
Alarm threshold: Threshold trigger value
-
Hysteresis: Hysteresis value for relay switching (prevents relay hunting)
-
Triggering direction:
Above: Means the relay contact is closed above the alarm threshold.
Below: Means the relay contact is open below the alarm threshold.
- $$$mode 1: réglage en
alarme
Use the
and
keys to select
the configuration required.
Select the
Relay adjustment
menu and press ENTER.
Use the
and
keys to select the
configuration required.
CONFIG
CONFIG
WHAT DO YOU WANT TO DO?
Averaging sensor response
Graphic screen
4-20mA outputs adjustment
Relay adjustment
Measure units
Language
Factory default value reminder
Configuration of the relays
mode:
- Mode 1: Alarms adjustment
- Mode 2: Regulation 2 relays
Esc: Escape menu
Enter: Validate the choice
Esc: Escape menu