panic or any damage in the building resulting from the test execution. The external signal
receivers and a monitoring centre must be notified of a planned test;
-
battery checking – pursuant to the manufacturer’s instructions.
-
battery condition checking – according to the battery manufacturer recommendations.
12.3
FUSE REPLACEMENT
The control panel is equipped with melt fuses in the following circuits:
-
reserve batteries charging – BZ1 3.15A of T3,15L250 V type;
-
external devices power supply – BZ3 1 A of F1L250 V type.
(BZ2 fuse is currently unused).
During the device proper operation, the fuse fault probability is very small. In case the allowable load
limits are exceeded, a melt insert fault may happen and it will be necessary to replace a fuse. The
fuse bases are accessible after the control panel door opening. The fuses are located in the MZ-4212
power supply unit module (Fig. 6).
13
PACKING, STORAGE AND TRANSPORTATION
Packaging
The control panel is placed in a unit packing, reducing free movement possibility and eliminating
damage occurrence during loading and transportation.
The following data are marked on the package:
-
the name and/or the trade mark of the manufacturer;
-
the name and the type of the control panel;
Additionally, the following marking is placed on the package:
“CAUTION FRAGILE”, “UPPER SIDE, DON’T TURN OVER”, “KEEP DRY” or equivalent marks according
to the PN-85/0-79252 Polish Standard.
Storage
The control panel should be stored in closed premises at a temperature b 5 0C and + 40 0C
and relative humidity not exceeding 80 %, free of corrosive vapours and gases. In case the control
panel is stored for a longer period, it is necessary to connect it to a power supply for at least 1 hour
and execute operation tests every 6 months.
During storage the control panel should not be exposed to heat radiation: direct sun light or heating
devices.
Transportation
The control panels should be carried in their packing by closed transport means, taking into
consideration the transport recommendations marked on the package, and protecting them against
sharp shocks and avoiding ambient temperature exceeding the – 25 0C to + 55 0C range.
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...