ID-E299-001GB
11
(21)
FUNCTION SW.OVER
, (22)
SELECTION
, (23)
SET
– three push buttons enabling usage of the
functions designated for the control panel parameters readout or change at the 2
nd
access level:
•
FUNCTION
– a function selection,
•
SELECTION -
moving the cursor to the right,
•
SET
- setting change.
4.2.2 Handling elements inside the control panel
Fig. 5 depicts the handling elements mounted on the STR-1240 controller board located inside the
control panel:
(P1)
FUNCTION
, (P2)
SELECTION
, (P3)
SET↑
and (P4)
SET↓
– four push buttons inside the control
panel that enable usage of the functions dedicated to the control panel programming;
(P13)
RESET
- the control panel controller restart.
Table 4
Jumper No.
Jumper position
Function
ZW1
1-2
Support of 16 detection lines – two line modules
2-3
Support of 24 detection lines – three line modules
ZW2
1-2
Unused
2-3
Unused
ZW3
1-2
2-3
ZW4
÷
ZW10
Unused
ZW11
1-2
2-3
Service mode without alarm receipt delays
ZW12
1-2
2-3
Software version display after pressing ACKNOWLEDGEMENT
push button
Fig. 6 presents the view of the MZ-4212 power supply unit module that contains:
WŁ. AKU
push button - used for switching the control panel on at the mains supply outage
(essential when the batteries connection does not cause the control panel self-activation);
ZW1
jumper
- enables disconnection the earth fault monitoring circuit and anti-interference
modules from the casing;
ZW2
- a jumper enabling the earth fault monitoring circuit switch on/off; when the jumper is set
in the position marked on the board - the earth fault monitoring circuit is switched on;
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...