28
ID-E299-001GB
•
to measure resistance of detection, monitoring and alarm lines and compare with admissible
values;
•
to check the wires polarization (‘+’, ‘-‘) with the terminal descriptions in the control panel;
•
to check presence of end-of-line resistors on unused line clamps in the control panel
(detection lines – 5.6 kΩ; monitoring lines – 10 kΩ);
•
to measure the grounding resistance;
•
to check the programming jumper positions – see p. 7.2.2, Table 4.
After the control panel operation start, it is recommended to:
•
in the case of a fault mode signalling – silence the control panel by pressing of
ACKNOWLEDGEMENT push button and read out FAULTS in accordance with 5.2.4;
•
remove possible faults so that the control panel signals the quiescent mode and lack of
faults;
•
use programming functions described in p. 5.2 and p. 5.3 to configure the control panel, set
the current time and date;
•
test signalling diodes placed on the control panel doors – p. 5.8;
•
use the TESTING ON function to test fire detectors and manual call points;
•
check operation of the control panel, signalling devices and alarm devices after the alarm
mode evoking;
•
check operation of other external devices installed in the system;
•
measure voltage on battery clamps (in buffering mode – lack of LED indication on the power
supply module – voltage should amount to 27.1
÷
27.6 V;
•
reset the event memory – p. 5.3.4.
8.2
STANDARD CONFIGURATION LOADING
The IGNIS 1240 control panel is delivered to a customer with initially programmed operation
conditions determined by the manufacturer, described as the ‘standard configuration’. The control
panel programming by the customer changes the factory default settings optimally adapting its
parameters to the system needs and protected premises features. The control panel is provided with
a function that enables an automatic reset of the customer’s settings and a return to the standard
configuration.
In order to load the standard configuration it is necessary to:
-
open the control panel (3rd access level);
-
use the ‘standard configuration loading’ function in accordance with p. 5.3.5;
-
select the following display indication:
STANDARD CONF. – 0
using the internal FUNCTION
push button (by pressing it several times repeatedly);
-
enable the function by entering “1” with the SET^ push bu[on;
-
restart the control panel with the RESET push button.
-
The following control panel parameters are loaded after executing the above mentioned operations:
•
all zones are enabled;
•
all zone delays are enabled;
•
delay time is set at 1 min 30 sec;
•
all zones are assigned with the alarm variants of the 0 number;
•
external alarm option – 0;
•
monitoring line operation option – 0;
•
every zone (line) is matched with one zone relay of the same number as the zone number;
the relay actuation depends on the alarm mode in the zone;
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...